Honeywell IAQ Thermostat User Manual


 
Installation Guide
69-1816EFS—03 2
Installer setup
Setup function Settings & options (factory default in bold)
0110 Zone number 0 Not zoned
1–9 Zone number
0120 Year
(first two digits)
20 (2000-2099)
21 (2100-2178)
0130 Year
(second two digits)
06 (2006)
[Other options: 00-99]
0140 Month 6 [Other options: 1-12]
0150 Date 15 [Other options: 1-31]
0160 Schedule format 4 7-day programming
0 Non-programmable
0165 Restore Energy
Star schedule
0 No
1 Yes
0172 System type
1 Conventional
2 Heat pump
3 Heat only (no fan)
E Auto Discover **
0174 Cooling compressor
stages
1 1 stage of cool
[Other options: 0 or 2 stages, or E]
0176 Heat or Heat Pump
Aux stages
1 1 stage of heat
[Other options: 0, 2 or 3 stages, or E]
0180 Fan control
(conventional heat)
0 Gas/Oil heat (equipment controls heating fan)
1 Electric furnace (thermostat controls heating fan)
2 Equipment controls stage 1, thermostat controls stage 2+
E Auto Discover **
0190 Changeover valve
(O/B terminal)
0 O/B terminal controls valve in cooling
1 O/B terminal controls valve in heating
0200 Backup heat
(Aux & EmHeat)
E Auto Discover **
0 Electric backup heat
1 Fossil fuel backup heat
Installer setup
**See page 6
SCHED HOLD
TUE
FAN
AUTO
Inside
70
6
aM
6:00
SYSTEM
HEAT
1 Press SYSTEM Press DONE to save & exit
DONE
TUE
Inside
70
20
0120
Function Setting
Press s t to change
2 Press and hold for 5 seconds
3 Change settings (see p. 2-6)
DONE
TUE
Inside
70
20
0120
DONE CANCEL
TUE
aM
6:00
SYSTEM
HEAT