Honeywell AQ251 Boiler User Manual


 
AQUATROL ZONE SYNCHRONIZING BOILER RESET CONTROLS
69-1979—04 6
TROUBLESHOOTING
Power Disruption
The AQ251’s system and thermostat (zone settings)
parameters are stored in non-volatile memory and are
updated as they change.
When a power disruption or loss of power occurs, the system
configuration is retained in memory.
When power is restored, the AQ251 Control Panel enters
auto-detection mode, reads its previously-stored settings, and
initializes all AQUATROL network components according to
their saved parameters.
POWER DISRUPTION GREATER THAN 4 HOURS
If a power disruption lasts for more than 4 hours, the AQ251
will have discharged its internal super capacitor, and the
DATE and TIME OF DAY settings will need to be reset.
Upon restart, the AQ251 displays its clock settings as: YEAR
= 2008, MONTH = JAN, DATE = 1. The message PLS SET
DAY/TIME displays. This displayed message continues until
the DATE and TIME OF DAY are updated.
NOTE: If the power failure parameter is set to Backlight
(USER MENU > PREFERENCES/TIME), the LCD
backlight flashes repeatedly, along with the mes-
sage.
The AQ251 remains permanently in OCCUPIED (or Comfort)
mode until the DAY and TIME OF DAY are updated.
System Status and Error Codes
System status alerts and error messages display on the
System Status Page. These messages are shown in Table 2.
Table 2. LCD Status Notices and Error Messages.
LCD Display Parameter Meaning
A/C MIN. OFF TIME n/a The A/C compressor is disabled, because the minimum OFF time has not yet elapsed.
A/C MIN. ON TIME n/a The A/C compressor is active and the minimum ON time has not yet elapsed.
AUX IN EM. SHUT n/a Auxiliary Input's Emergency Shut Down is active.
BOILER: EM SHUT Boiler is disabled, because the AQ251 is in Emergency Shut Down mode.
FRZ PROT Boiler freeze protection activated:
Communication between Control Module and Zoning Module has been lost for more
than 1 minute
or
Boiler supply temperature is less than 50°F (10°C)
HEAT DHW Boiler is active to serve DHW.
HEATING Boiler is active to serve zones.
IDLE Boiler is not active.
INIT Boiler contacts (terminals 22 and 23) on the AQ1520, which are connected to the
boiler's T-T terminals, have been shorted and the boiler is beginning its firing sequence.
INST PURG Boiler is active while the AQ251 is conducting the PURGE operation in the Installer
Setup.
NSTALL Boiler is in ready mode during Installer Setup.
PMP EXER Boiler is disabled while the AQ251 is exercising all pumps and valves connected to the
AQUATROL network.
POST PURG Boiler is active with Post Purge operation and is sending the purged water to the Boiler
(Primary) loop.
PURGE DHW Boiler is active with Post Purge operation and is sending the purged water to the DHW
tank.
CALL FOR COOL n/a At least one zone with a programmable thermostat requires cooling.
CALL FOR DHW n/a The DHW requires heat.
CALL FOR HEAT n/a At least one zone requires heat.
CWSD ACTIVE n/a Zone calls for cooling are not served because CWSD (Cold Weather Shutdown) is in
progress.
DHW DISABLE n/a DHW call is not served because it is disabled.
LOST ZONE A-1
LOST ZONE D-16
n/a Lost communication with a zone (A-1 to A-16, B-1 to B-16, C-1 to C-16, or D-1 to D-16).
NO DHW PROBE n/a No DHW sensor connected or it is defective.
NO OUTDOOR PROBE n/a No outdoor sensor connected or it is defective.