Herrmidifier Co 6000 Humidifier User Manual


 
Key Features
Adjustable Setpoints
Capacity
Range = 50-100%
Preset at 100% for 6000-1,3,4
Preset at 50% for 6000-2
Low Drain Threshold
Range = 50-100%
Preset at 90%
Cycle Time
Range = 60-300 seconds
Preset at 60 seconds
Faults
Overcurrent
138% of Rated Current
System Shutdown
Fill System
Fill valve open for 6 hours without achieving capacity setpoint or cylinder full
System Shutdown
End of Cylinder Life
6 hours of operation while on cylinder full without achieving capacity setpoint
System Shutdown (See Pg. 14 for Manual Override)
Conductivity*
Micromhos
(approx.)
Average Life**
Expectancy – Hrs.
(approx.)
100 2000
135 1900
170 1800
250 1300
500 800
750 650
1000 500
*If the conductivity of your supply water is less than 100 micromho, consult Herrmidifier for specific circuit board
adjustments and replacement tank information (GT-176-1).
Unit performance may be affected.
Operation on water of less than 60 micromho is not recommended.
**Your actual cylinder life may be higher or lower depending on the exact composition of your water supply.