Air Pressure Drops- Cabinets, Filters, Wet Coils
Cabinet And Filter Air Pressure Drop
Air Pressure Drop - inches of water Air Velocity^ - Feet per minute
Component 200 250 300 350 400 450 500 550 600
Cabinet: V Style Cabinet^^ .10 .13 .16 .20 .24 .29
Economizer Section^^ .02 .03 .03 .04 .05 .06 .07
Filters: Throwaway 2" Depth .05 .08 .11 .15 .19 .24 .28 —— ——
flat & hi 35% Efficient , Pleated 2" Depth .08 .10 .13 .16 .21 .25 .30 .37 ——
capacity Permanent, Aluminum, Cleanable 2" Depth .03 .04 .06 .08 .10 .13 .15 .18 .21
flat, 4" 35% Efficient , Pleated 4" Depth .06 .07 .10 .13 .17 .20 .25 .29 .34
(60 - 65%) Efficient 21" Depth .12 .16 .21 .26 .32 .38 .45
Filters: Bag Filter 30" Depth .19 .24 .28 .33 .37 .41 .44
37" Depth .12 .17 .23 .27 .33 .37 .41
Medium (80 - 85%) Efficient 21" Depth .14 .20 .26 .32 .38 .44 .51
Bag Filter 30" Depth .23 .28 .34 .40 .47 .51 .55
37" Depth .15 .21 .26 .32 .38 .45 .52
and (90 - 95%) Efficient 21" Depth .20 .28 .36 .44 .52 .61 .70
Bag Filter 30" Depth .32 .39 .46 .53 .60 .66 .72
37" Depth .22 .29 .36 .44 .54 .60 .68
High (60 - 65%) Cartridge Filter 6" Depth .15 .20 .26 .33
12" Depth .22 .28 .34 .41 .50 .58 .68
(80 - 85%) Cartridge Filter 6" Depth .22 .29 .37 .46
Efficiency 12" Depth .26 .32 .38 .46 .55 .64 .74
(90 - 95%) Cartridge Filter 6" Depth .25 .34 .44 .56
12" Depth .29 .35 .42 .50 .59 .70 .82
The filter air pressure drop is for air through clean filters.
Type A (1/2" O.D.) Wet Coil Air Pressure Drop* Type 5 (5/8" O.D.) Wet Coil Air Pressure Drop*
Rows Fin Air Velocity - Feet per minute^ Rows Fin Air Velocity - Feet per minute^
Series 400 450 500 550 600 650 Series 400 450 500 550 600 650
6 0.18 0.22 0.26 0.30 0.34 0.39 6 0.25 0.30 0.36 0.42 0.49 0.56
8 0.22 0.27 0.32 0.37 0.42 0.48 8 0.31 0.37 0.44 0.52 0.60 0.68
3 10 0.26 0.32 0.37 0.43 0.50 0.56 3 10 0.36 0.44 0.52 0.58 0.67 0.79
12 0.30 0.37 0.43 0.50 0.57 0.65 12 0.42 0.50 0.59 0.66 0.76 0.87
14 0.34 0.41 0.49 0.56 0.64 0.73 14 0.45 0.54 0.64 0.74 0.85 0.97
6 0.24 0.29 0.35 0.40 0.47 0.53 6 0.33 0.40 0.48 0.56 0.65 0.74
8 0.30 0.36 0.43 0.50 0.57 0.65 8 0.41 0.50 0.59 0.69 0.80 0.91
4 10 0.35 0.43 0.51 0.59 0.67 0.77 4 10 0.48 0.58 0.69 0.81 0.93 1.06
12 0.41 0.49 0.58 0.68 0.77 0.88 12 0.56 0.67 0.79 0.92 1.02 1.20
14 0.46 0.56 0.66 0.76 0.87 0.99 14 0.63 0.75 0.89 1.03 1.14 1.34
6 0.31 0.38 0.45 0.53 0.61 0.70 6 0.41 0.50 0.60 0.70 0.81 0.93
8 0.39 0.47 0.56 0.65 0.74 0.84 8 0.51 0.62 0.74 0.86 0.99 1.13
5 10 0.46 0.55 0.65 0.75 0.86 0.97 5 10 0.60 0.73 0.87 1.01 1.12 1.32
12 0.53 0.63 0.74 0.85 0.97 1.10 12 0.69 0.84 0.99 1.11 1.27 1.50
14 0.59 0.71 0.83 0.95 1.09 1.22 14 0.78 0.94 1.11 1.24 1.42 1.68
6 0.37 0.46 0.54 0.64 0.74 0.84 6 0.49 0.60 0.72 .84 0.98 1.12
8 0.46 0.56 0.67 0.78 0.90 1.03 8 0.61 0.74 0.88 1.03 1.19 1.36
6 10 0.55 0.67 0.79 0.92 1.05 1.18 6 10 0.72 0.88 1.04 1.21 1.40 1.59
12 0.63 0.77 0.90 1.04 1.19 1.34 12 0.83 1.01 1.19 1.38 1.59 1.80
14 0.72 0.86 1.01 1.17 1.33 1.49 14 0.94 1.13 1.33 1.55 1.77 2.01
6 0.51 0.62 0.74 0.87 0.99 1.12 6 0.66 0.80 0.96 1.12 1.30 1.49
8 0.63 0.77 0.90 1.05 1.20 1.35 8 0.82 0.99 1.18 1.38 1.59 1.82
8 10 0.75 0.90 1.06 1.23 1.40 1.58 8 10 0.97 1.17 1.39 1.62 1.86 2.12
12 0.86 1.03 1.21 1.40 1.59 1.79 12 1.11 1.34 1.58 1.84 2.12 2.41
14 0.96 1.15 1.35 1.56 1.78 2.01 14 1.25 1.51 1.78 2.06 2.36 2.68
* Wet coil air pressure drop for air entering at 80 °F DB and 67 °F WB over rippled high efficiency fins. Inches of water.
^ Air velocity = CFM divided by coil or filter face area in square feet. See table at top of page 40.
^^ Use face area of large coil to calculate air speed through AHV cabinet and economizer section.