Heatcraft Refrigeration Products HCS Air Conditioner User Manual


 
39
TA= Throw away type filters
AF= Airfoil Fan
FC= Forward Curved fan
Double wall construction add 45% to
fan & Coil section or accessory
Net Weights and Metal Gauges
Air Handler Component Unit Size
Weight in pounds 03 06 08 10 12 14 18 20 26 34 41 50 65 75
HCS short FC 290 430 500 550 650 790 816 836 968 1188 1386
Fan HCS short AF 946 1177 1518 1782 2700 3300 4496
HCL long FC 318 450 553 600 732 988 1033 1067 1221 1474 1672
and HCL long AF 1177 1430 1793 2057 2850 3480 4690
VCS vertical FC 296 387 482 535 615 860 1004 1111 1254 1628 1881
Coil HD heating duty FC 170 280 312 360 450 510 564 605 693 902 1078
HD heating duty AF 715 891 1221 1474 2600 3200 3359
Sections
Flat - TA & Pleated 2" 60 73 83 95 99 104 106 108 115 160 185 255 315 384
Flat - Permanent 2" 66 79 89 101 106 114 126 135 165 240 275 390 460 560
Filter Flat - Pleated 4" 75 88 98 110 119 124 126 127 130 185 210 298 351 428
High Capacity - TA & Pleated 149 168 187 206 215 224 230 234 244 260 290 360 440 535
Sections High Capacity - Permanent 155 176 196 216 225 234 240 244 254 365 450 520 650 790
High Efficiency - 22" Section 82 95 112 133 133 153 175 180 194 235 248 269 330 359
High Efficiency - 28" Section 103 121 143 170 170 196 225 224 246 296 318 345 425 463
High Efficiency - 44" Section 127 150 173 201 201 230 264 274 299 358 380 412 516 552
Mixbox 174 195 216 224 236 247 254 260 300 430 550 680 800 975
Other
Accessory Internal Face and Bypass 52 68 79 100 115 138 148 155 180 260 350 420 520 634
Sections External Face and Bypass 57 75 87 110 128 155 166 175 200 286 385 462 650 793
Auxiliary Coil Module HCS 129 164 204 208 223 306 280 261 310 331 362 515 640 1305
Auxillary Coil Module HCL 157 184 257 258 305 504 497 492 563 617 648 665 820 1499
Electric Heater 199 218 237 266 285 294 310 314 324 355 390 485 590 685
1 Row 36 55 70 80 94 106 110 112 144 195 239 339 406 538
2 Row 50 80 101 120 143 164 169 173 228 318 396 562 673 891
Large Type 5 3 Row 64 106 134 161 195 223 231 236 314 444 557 737 936 1168
4 Row 78 132 168 202 246 282 292 299 398 569 718 913 1199 1445
Coils 10 FPI 6 Row 109 187 240 290 353 408 422 432 578 830 1052 1278 1677 2017
8 Row 141 242 311 379 461 534 552 565 760 1092 1385 1638 2154 2589
10 Row 172 297 383 467 569 659 682 699 942 1355 1718 2194 2893 3478
(Coil weights include the weight of water when filled)
To estimate weights for other coils:
For Type A: multiply type 5 coil weight by 0.800
For Small coil : multiply large coil weight by 0.823
For 14 FPI: multiply 10 FPI coil weight by 1.121
For 12 FPI: multiply 10 FPI coil weight by 1.065
For 8 FPI: multiply 10 FPI coil weight by 0.935
For 6 FPI: multiply 10 FPI coil weight by 0.915
Air Handler Motor And Drive Motor Horsepower, 1800 RPM
Weight in pounds 1 1.5 -2 3 5 7.5 10 15 20 25 30 40 50
Motor & High Efficiency Open Single Speed 67 74 114 127 209 216 341 384 396 427 621 623
Drive Totally Enclosed Fan Cooled (TEFC) 56 71 88 104 178 194 275 336 411 461 624 670
Weight Open 2 Speed, 2 Winding 71 97 115 160 291 267 368 356 366
Air Handler Panels And Frames Unit Size
Description, metal gauge 03 06 08 10 12 14 18 20 26 34 41 50 65 75
Frame 12 12 12 12 12 12 12 12 12 12 12 10 10 10
Fan Fan Panel 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Section Side Panel 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Bottom Panel 14 14 14 14 14 14 14 16 16 16 16 16 16 16
Frame 14 14 14 14 14 14 14 14 14 14 14 10 10 10
Coil Top Panel 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Section Bottom Panel 14 14 14 14 14 14 14 16 16 16 16 16 16 16
Drain Panel 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Accessory Filter Section Casings 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Sections Economizer Casings 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Damper Blades 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Others Removable Panels 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Base Rails 10 10 10 10 10 10 10 10 10 10 10 08 08 08