Heat & Glo LifeStyle 8000TV-OAK Gas Heater User Manual


 
12 Heat & Glo • 8000TV-OAK, 8000TV-OAK-IPI, 8000TVLP-OAKIPI • 2058-900 Rev. L • 08/08
Roof Pitch H (Min.) Ft.
Flat to 6/12...........................................................1.0*
Over 6/12 to 7/12 .................................................1.25*
Over 7/12 to 8/12 .................................................1.5*
Over 8/12 to 9/12 .................................................2.0*
Over 9/12 to 10/12 ...............................................2.5*
Over 10/12 to 11/12 .............................................3.25
Over 11/12 to 12/12 .............................................4.0
Over 12/12 to 14/12 .............................................5.0
Over 14/12 to 16/12 .............................................6.0
Over 16/12 to 18/12 .............................................7.0
Over 18/12 to 20/12 .............................................7.5
Over 20/12 to 21/12 .............................................8.0
Figure 4.1 speci es minimum vent heights for various
pitched roofs.
* 3 foot minimum in snow regions
18 IN.
A
8 FEET
(MINIMUM) TO
PERPENDICULAR
WALL (GAS ONLY)
GAS OR WOOD
TERMINATION
GAS
TERMINATION
VERTICAL
WALL
TERMINATION
CAP
12
X
ROOF PITCH
IS X/ 12
LOWEST
DISCHARGE
OPENING
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
8 FEET
Termination Clearances
Gas Wood
A 6 inches 20 inches
A. Vent Termination Minimum Clearances
Fire Risk.
Explosion Risk.
Maintain vent clearance to combustibles as
speci ed.
Do not pack air space with insulation or other
materials.
Failure to keep insulation or other materials
away from vent pipe may cause re.
4
4
Termination Locations
WARNING
Figure 4.1 Minimum height from roof to lowest discharge
opening
Figure 4.2 Multiple Vertical Termination