Part 4 Trouble Shooting
9) Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65
41
44
45
46
47
65
Discharge pipe sensor
(Inverter)
Air sensor
Condenser Pipe sensor
Suction Pipe sensor
Discharge pipe sensor
(Constant)
Heat sink sensor
Open / Short
Soldered poorly
Internal circuit error
Open / Short
Soldered poorly
Internal circuit error
Open / Short
Soldered poorly
Internal circuit error
Open / Short
Soldered poorly
Internal circuit error
Open / Short
Soldered poorly
Internal circuit error
Open / Short
Soldered poorly
Internal circuit error
Normal resistor : 200k / at 25°C(77°F) (Unplugged)
Normal voltage : 4.5VDC / at 25°C(77°F) (plugged)
Normal resistor : 10k / at 25°C(77°F) (Unplugged)
Normal voltage : 2.5VDC / at 25°C(77°F) (plugged)
Normal resistor : 5k / at 25°C(77°F) (Unplugged)
Normal voltage : 2.5VDC / at 25°C(77°F) (plugged)
Normal resistor : 5k / at 25°C(77°F) (Unplugged)
Normal voltage : 2.5VDC / at 25°C(77°F) (plugged)
Normal resistor : 200k / at 25°C(77°F) (Unplugged)
Normal voltage : 4.5VDC / at 25°C(77°F) (plugged)
Normal resistor : 10k / at 25°C(77°F) (Unplugged)
Normal voltage : 2.5VDC / at 25°C(77°F) (plugged)
Display
code
Title Cause of error Check point & Normal condition
Check Point
1. Estimate the resistance of each sensor.(Unplugged)
2. Estimate the voltage of each sensor.(Plugged)
3. If the resistance of the sensor is 0 k or , then sensor is abnormal.
If the voltage of the sensor is 0 V or 5VDC, then sensor is abnormal.