Heat Controller VMC18SB-1/VMH18SB-1 Heat Pump User Manual


 
- 15 -
Only for training and service purposes
Part 2 Functions & Controls
5.1 Five Seconds Stand-by (fan)
The indoor unit fan will begin to rotate after 5 seconds of the unit being turned on.
5.2 Two Minutes Stand-by (comp.)
After the compressor cycles off, it will not restart for a minimum of 2 minutes.
5.3 Hot start Heatpump Only
To prevent cold air from blowing in the room upon starting up the unit in heating mode, the indoor fan will not rotate
until the heat exchanger temperature reaches 30˚C(86˚F).
5.4 Freeze prevention (Protection of the evaporator pipe from frosting)
Heatpump Only
If the indoor pipe temperature is below 0˚C(32˚F) within 7 minutes after the compressor operates continuously in cool-
ing mode, the compressor and outdoor fan will turn off.
When the indoor pipe temperature is 7˚C (44.6˚F) or higher after a 2 minute pause/cycle off of the compressor, the
compressor and outdoor fan will turn on according to the condition of the indoor air temperature.
5. Protection Functions & Controls
Comp. free
Comp. Step 4
Comp. Step 2
Comp. off
T1
3˚C(37.4˚F)
6˚C(42.8˚F)
7˚C(44.6˚F)
Indoor pipe
temp.
T1: 0 ~ 2°C(32~35.6°F)
NOTE: Some Models are different by T1.