Heat Controller VMC18SB-1/VMH18SB-1 Heat Pump User Manual


 
- 13 -
Only for training and service purposes
Setting temp. (˚C)
1.0˚C(2˚F) up
1.0˚C(2˚F) up
Cooling ON temp.
(Setting temp. +0.5˚C(+1˚F))
Cooling OFF temp.
(Setting temp. -0.5˚C(-1˚F))
0.5 1 Sleep time
(
hour
)
Part 2 Functions & Controls
4.3 Air volume control
Indoor fan motor control have 6 steps.
Air volume is controlled "SH", "H", "Med", "Low" by the remote con-
troller.
"LL" step is selected automatically in Hot start operation.
4.4 Natural Air Control(Auto Wind)
When the Auto Step is selected, the high, medium, or low speed of
the airflow mode is operated for 2~15 sec. randomly by the Chaos
Simulation.
4.5 Chaos Swing
By selecting Chaos swing, the horizontal vane automatically operates with a swinging motion or it is fixed to the
desired direction.
4.6 Sleep mode Auto control
Using the remote control, the sleep mode timer can be set for a time period of 1,2,3,4,5,6 or 7 hours. During this time
period the unit will operate as described in sections 4.6.1 or 4.6.2, until the set time period has expired. Once the set
time period has been reached, the unit will automatically turn off.
When the appliance is on pause, the sleep timer mode cannot be input.
4.6.1 Sleep timer operation for cooling cycle
While in cooling mode , 30 min. after the start of the sleep timer, the setting temperature increases by 1 C(2 .
After another 30minutes lapse, it increases again by 1°C(2 .
LL Very low, In heating mode
L Low
M Med
H High
SH Super high
Auto Natural wind
Step Description
NOTE: Some Models are different by swing width and swing pattern.