Heat Controller BHD-501-G Dehumidifier User Manual


 
Heat Controller, Inc. Portable Dehumidier with R-410A BHD-G Service Manual
10
CAPACITOR - TEST
1. Remove capacitor from unit.
2. Check for visual damage such as bulges, cracks, or leaks.
3. For dual rated, apply an ohmmeter lead to common (C) terminal and the other probe to the compressor
(HERM) terminal. A satisfactory capacitor will cause a deection on the pointer, then gradually move back to
innity.
4. Reverse the leads of the probe and momentarily touch the capacitor terminals. The deection of the pointer
should be two times that of the rst check if the capacitor is good.
5. Repeat steps 3 and 4 to check fan motor capacitor.
NOTE: A shorted capacitor will indicate a low resistance and the pointer will move to the “0” end of the scale and
remain there as long as the probes are connected.
An open capacitor will show no movement of the pointer when placed across the terminals of the capacitor.