Hearth and Home Technologies SL-750TRS-IPI-E Indoor Fireplace User Manual


 
Heat & Glo • SL-750TRS-IPI-E, SL-550TRS-IPI-E, SL-350TRS-D, SL-350TRS-IPI • 2120-900 Rev. D • 6/07 25
A* B* C D
SL-750TRS-IPI-E
Inches
41 27-7/8 40 26-7/8
Millimeters
1041 708 1016 683
SL-550TRS-IPI-E
Inches
36-1/2 24-3/8 35-1/2 23-3/8
Millimeters
927 619 902 594
SL-350TRS-D
Inches
35-1/2 22-3/8 34-1/2 21-3/8
Millimeters
902 568 876 543
Combustible Wall Penetration
Frame a hole in a combustible wall for an interior wall
shield restop, (Figure 6.2) whenever a wall is penetrated.
Use same size framing materials as those used in the wall
construction. The wall shield restop maintains minimum
clearances and prevents cold air in ltration.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncombus-
tible materials such as concrete, a hole with diameter one
inch greater than the pipe is acceptable.
B. Wall Penetration Framing
Figure 6.3 Exterior Wall Hole
* Shows center of vent framing hole for top or rear venting.
The center of the hole is one (1) inch (25.4 mm) above the
center of the horizontal vent pipe.
C
D
B*
A*
6
6
Vent Clearances and Framing
WALL
HEAT
SHIELD
HEAT
SHIELD
3in.TOP
CLEARANCE
WALL
SHIELD
FIRESTOP
1in.CLEARANCE
BOTTOM & SIDES
7in.
A. Pipe Clearances to Combustibles
Fire Risk.
Explosion Risk.
Maintain vent clearance to combustibles as
speci ed.
Do not pack air space with insulation or other
materials.
Failure to keep insulation or other materials
away from vent pipe may cause re.
Figure 6.1 Pipe Clearances
1 in. CLEARANCE
AROUND VERTICAL
SECTIONS
3 in. TOP
CLEARANCE
1 in. SIDE AND
BOTTOM CLEARANCE
Note: Slope
not required.
WARNING
Figure 6.2 DVP Horizontal Venting Clearances to Combustible
Materials
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).
The heat shield is designed to be used on a wall 4 in. to 7-1/4 in. (102 mm
to 184 mm) thick. If wall thickness is less than 4 in. (102 mm) the existing
heat shields must be eld trimmed. If wall thickness is greater than 7-1/4
in. (184 mm) a DVP-HSM-B will be required.
Note: When using SL pipe, minimum clearances from the vent pipe to
combustible materials at wall restops are:
Top: 2-1/2 inches
Bottom: 1/2 inch
Sides: 1 inch