C. Install the Ceiling Firestop
A ceiling restop MUST be used between
oors and attics.
Frame opening 9 in. x 9 in. (229 mm x
229 mm) whenever the vent penetrates
a ceiling/floor (see Figure 8.3).
Frame the area with the same sized lumber
as used in ceiling/ oor joist.
• The ceiling restop may be installed above
or below the ceiling joists when installed
with a attic insulation shield. It must be
under joists between oors that are not
insulated. Refer to Figure 8.4.
Secure with three fasteners on each side.
WARNING! Risk of Fire! DO NOT pack
insulation around the vent. Insulation must be
kept back from the pipe to prevent overheat-
ing.
Figure 8.3 Installing Ceiling Firestop
Figure 8.4 Installing the Attic Shield