Hearth and Home Technologies CNXT4236IH Indoor Fireplace User Manual


 
Heatilator • Caliber CNXT Series • 4047-132 Rev U • 11/08 57
I. WSK-MLT Operating Instructions
The ON/OFF rocker switch in the replace (located near
the gas valve) must be in the “OFF” position for use with
the WSK-MLT system. The ON/OFF rocker switch will
NOT function with this device on Intelli re (IPI) mod-
els except during a power outage. The ON/OFF rocker
switch will only be used to control the replace in a no-
power condition.
After all connections are made and the control box is
grounded, plug power cord into the replace junction box.
The wall switch will be functional at this time.
For IPI system, refer to “Operation Under Battery Power”
for instructions.
Note: The temperature displayed by the wall switch may
take up to 30 minutes to stablize on initial power-up.
Note: Check control box and assure switch is in the “OFF”
position. This switch is only used on Intelli re (IPI) control
systems under battery operation.
J. Setting Flame Height/Manifold Pressure
(To be done by a quali ed service technician.) Upon initial
power-up of this device, valve pressure must be set for
ame adjustment.
Loosen output pressure tap on valve and connect with
pressure manometer.
• Press ame button once (see Figure 12.8); replace will
light with ames on high.
Turn solenoid clockwise to increase pressure,
counterclockwise to decrease pressure until manifold
pressure on high is 3.5 in. water column for natural gas
(NG), 10.0 in. water column for propane (LP).
Once pressure is achieved sping jam nut on solenoid
step tight against regulator face to prevent rotation. Do
not overtighten.
• Press ame button twice to turn replace off.
Remove manometer tube and tighten or close pressure
tap. Use a commercially available, non-corrosive leak
check solution to carefully check the pressure tap for
leaks. Be sure to rinse off all leak check solution following
testing.
Figure 12.8 Wall Switch
K. Wall Switch Button Operation
(Refer to Figure 12.8.)
Flame Button
Button Press: Unit On / Flames High, turns on auxilary
power
Button Press: Flames Low
Button Press: Unit Off / Flames Off, turns off auxilary
power
Fan / Blower Button
Button Press: Fan High (“3”)
Button Press: Fan Medium (“2”)
Button Press: Fan Low (“1”)
Button Press: Fan Off
Temperature Button
Button Press will toggle between Automatic and Manual
Operation.
Press and Hold the button for 3 seconds to toggle
between Fahrenheit and Centigrade Temperature
Display.
Automatic Operation: Controller will monitor temperature
and control unit according to the set point.
Manual Operation: Controller will not automatically change
settings.