Hearth and Home Technologies 6000GBV-IPILP Indoor Fireplace User Manual


 
Heat & Glo • 6000GBV, 6000GBV-IPI • 2104-900 Rev. H • 11/08 23
7
7
Vent Information and Diagrams
B. Vent System Con guration
CAUTION! Risk of Fire! ALL vent con guration speci -
cations MUST be followed. This product is tested and listed
to these speci cations. Appliance performance will suffer if
speci cations are not followed.
Rise to Run Ratio = 2:1
Maximum Total Horizontal Run = 15 Feet
Minimum Total Vertical Rise = 9 Feet
Maximum Total Vertical Rise = 30 Feet
Maximum Number of Elbows: Two 90º or Four 45º
Figure 7.1
A. Vent Guidelines
WARNING! Fire Risk/Asphyxiation! This appliance requires
the speci ed pipe for operation. Incorrect pipe may cause spill-
age, condensation and overheating.
Figure 7.2
These models require the following size B-vent double
wall, or single wall rigid or ex vent pipe.
METAL
PLUMBERS' STRAP
MAXIMUM HORIZONTAL RUN IS 50%
OF VERTICAL. HORIZONTAL RUN
CANNOT BE MORE THAN 15 FT
.
VENT SUPPORTS
ARE PER VENT
MANUFACTURER'S
SPECIFICATIONS.
METAL
PLUMBER’S
STRAP
9 FEET
MINIMUM
VENT SUPPORTS ARE PER
VENT MANUFACTURER’S
SPECIFICATIONS
MINIMUM CLEARANCES
ARE PER VENT
MANUFACTURER’S
SPECIFICATIONS
Follow pipe manufacturer’s installation guidelines when
installing the appliance.
WARNING!
Fire Risk/Explosion/Asphyxiation! DO NOT
connect this gas appliance to a chimney ue serving a
separate solid-fuel or gas burning appliance.
• Vent this appliance directly outside.
• Use separate vent system for this appliance.
May impair safe operation of this appliance or other appli-
ances connected to the ue.
WARNING! Risk of Fire or Explosion! Insulation and oth-
er combustibles must not infringe on clearances.
• ALWAYS maintain speci ed clearances around venting and
restop systems.
• Install restops as speci ed.
Failure to keep insulation or other material away from vent pipe
may cause re.
Figure 7.3
45 DEGREES
ELBOW
90 DEGREES
ELBOW
OFFSETS EXCEEDING
45 DEGREES ADAPT
HORIZONTAL LIMITATIONS
MAXIMUM
HORIZONTAL
15 FEET
MINIMUM
VERTICAL
9 FEET
Note: Maximum horizontal
distance is 50% vertical vent
height.
Note: Horizontal runs must have
minimum rise in accordance with
mechanical codes.
Model Pipe Size
6000GBV 6 inch
6000GBV-IPI 6 inch