Harman Stove Company SF160 Boiler User Manual


 
8
3feet(0.9m)abovethepointatwhichtheyexit
fromtheroof,itmustalsoextend2feet(0.6m)
abovethehighestpointwithina10ft.(3m)radius.
DO NOT CONNECT THIS UNIT TO A CHIMNEY
FLUE THAT IS SERVING ANOTHER APPLIANCE.
Limitconnectorpipeto8ft.orless,with
nomorethantwoelbows.Allhorizontalsections
shouldhave1/4in.riseperfoot.Thechimney
mustbecapableofprovidingadraftreadingofat
least.06in.ofwatercolumn.Abarometricdamper
canbeinstalledtopreventexcessiveanderratic
draft.Allconnectorpipeshouldbesecuredwith
sheetmetalscrewsateachjoint.
Installation
Plumbing
TheHarmanTridentBoilercanbeusedas
a“StandAlone”boilerorasanadd-ontoanexist-
inghotwaterheatingsystem.
Thediagramsinthismanualaremeantto
showthenecessaryequipmentandpiping.Your
systemmaylookverydifferent.However,ifcong-
uredproperly,thesameresultswillbeachieved.
Fig.6showsatypicalplumbingdiagram
fortyingintoanexistingsystem.Thismethod
provideswatercirculationbetweenthetwoboilers
withacirculatingpump.Inthissetup,thedomes-
ticwatercoilintheexistingboilerwillbeheated,
makingitunnecessarytoinstallawatercoilinthe
Trident Boiler.
Tying-intoanexistingboilermustbedone
inthereturnlinebetweenthecirculatorandthe
existingboiler.Runapipefromtheretoasmall
circulator,andthenintothe1-1/4in.ttingonthe
rearoftheTridentBoiler.Nextrunapipefromthe
1-1/4in.ttingonthetopoftheTridentBoilertoa
Teettinginthesupplylineoftheexistingboiler.
ThisTeettingmustbeinstalledbetweentheex-
istingboilerandtheFlowControlValve,asshown
inFig.6.Anairvalveshouldbeinstalledonthis
line also.
FIG.5
FIG.6
Air Valve
Notice:
The Aquastat controls supplied with
the Trident Boiler are designed only
to maintain water temperature within
the boiler. The actual heating sys-
tem is controlled separately by your
thermostat(s) opening zone valves or
energizing circulation pump(s).
Do not attach a thermostat to the sup-
plied controls.