Harman Stove Company 2 Stove User Manual


 
14
#1 Preferred method
This method provides excellent venting for nor-
mal operation and allows the stove to be installed
closest to the wall. Two and a half inches from the
wall is safe; however, three inches allows better
access to remove the rear panel. The vertical por-
tion of the vent should be three to five feet high. This
vertical section will provide natural draft in the event
of a power failure. Note: Do not place joints within
wall pass-throughs.
Fig.25
Fig.26
Venting
KEEP COMBUSTIBLES (SUCH AS
GRASS, LEAVES, ETC.) AT LEAST 3
FEET AWAY FROM THE FLUE OUTLET
ON THE OUTSIDE OF THE BUILDING.
CAUTION
3 ft.
to combustibles
#2 Preferred method
This method also provides excellent venting for
normal operation but requires the stove to be installed
farther from the wall. The vertical portion of the vent
should be three to five feet high and at least three
inches from a combustible wall. This vertical sec-
tion will provide natural draft in the event of a power
failure. Note: Do not place joints within wall pass-
throughs.
Combustibles
allowed
beyond 3 ft.
3 ft.
to combustibles
Combustibles
allowed
beyond 3 ft.
3 ft.
to combustibles
3 ft.
to combustibles
Evaluation notes were added to the output document. To get rid of these notes, please order your copy of ePrint IV now.