Harman Stove Company 1-90-79700 Indoor Fireplace User Manual


 
12
Dry Seasoned Wood Only! 3-90-798 Save These Instructions


The appliance legs may not be removed
for installation.
Minimum Size oor protection (USA) is 48" Deep By
32.5" Wide.

If the Oakleaf is being installed on a combustible
oor, the bottom heat shield (part # 1-00-797058) must
be installed along with proper oor protection material.
(See page 25). Floor protection must be a minimum
3/8" (9.5mm) thickness of material having an insulating
value equal to or better than 0.84k/in. (The lower the k
value, the better the protection.)
Another method for calculating oor protection is in
R value. This requirement would be for an R value of
0.45 or higher. (The higher the R value, the better the
protection). Example- 1 inch of Durock® = 0.52R
In all installations, the area under and around the
stove must be protected from falling ash and live coals.
The area under a horizontal run of chimney connector
must also be protected, extending two (2) inches
beyond the measurement of the horizontal connector.
Further guidelines for oor protection are as follows:
In the U.S. the oor protector must be completely
under the stove, and extending 16" in front of the door
opening, 8" to each side and 8" to the back.
In Canada, the oor protection must extend 18"
(457mm) in front of the door opening, 8" (203mm) to
each side and extend to the wall behind the stove.


Inches Millimeters
Sides- USA /CANADA *
Rear- USA
8 203
8 203
Rear- CANADA
Wall Wall
Front- USA /CANADA *
18 457
* Floor protection for the front and sides as measured
from the appliance door opening.

Minimum 60" corner oor protection (USA & CANADA).