Goodmans CPG SERIES Air Conditioner User Manual


 
31
APPENDIX A BLOWER PERFORMANCE TABLES
BELT DRIVE
HIGH STATIC DOWN SHOT
CPG036 HIGH STATIC BELT DRIVE DOWN SHOT
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6
1655 0.526 1389 0.395 1103 0.275
0.8
1640 0.571 1342 0.426 1035 0.289 775 0.19
1.0
1638 0.632 1326 0.471 1002 0.317 713 0.192
1.2
1638 0.692 1307 0.519 984 0.362
1.4
1307 0.579 1002 0.416
1.6
1002 0.476 717 0.319
1.8
717 0.379
CPG048 HIGH STATIC BELT DRIVE DOWN SHOT
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6
1989 0.769 1712 0.594 1433 0.441
0.8
1929 0.788 1662 0.631 1384 0.469 1106 0.329
1.0
1952 0.876 1622 0.665 1335 0.494 1056 0.345
1.2
1897 0.93 1611 0.726 1315 0.543 1008 0.357
1.4
1616 0.80 1298 0.588 1007 0.419
1.6
1316 0.659 1007 0.46
1.8
CPG060 HIGH STATIC BELT DRIVE DOWN SHOT
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6
2262 1.161 2051 0.948 1851 0.763 1657 0.60
0.8
2277 1.271 2070 1.048 1852 0.837 1646 0.656
1.0
2304 1.387 2089 1.153 1872 0.931 1647 0.722
1.2
2104 1.255 1893 1.029 1668 0.811
1.4
1912 1.129 1690 0.90
1.6
1720 1.00
CPG072 HIGH STATIC BELT DRIVE DOWN SHOT
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6
2793 1.645 2575 1.367 2407 1.155 2250 0.963
0.8
2775 1.762 2638 1.526 2407 1.253 2226 1.045 2011 0.835
1.0
2821 1.894 2660 1.668 2407 1.358 2194 1.116 2012 0.923
1.2
2696 1.787 2497 1.54 2228 1.235 1977 0.985
1.4
2455 1.591 2236 1.346 2013 1.10
1.6
2262 1.44 2032 1.20
1.8
2069 1.30
NOTE
ESP, In
H
2
O
TURNS OPEN
012345
TURNS OPEN
ESP, In
H
2
O
450123
ESP, In
H
2
O
TURNS OPEN
012345
Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P.
SCFM correction for wet coil = 4 %.
ESP, In
H
2
O
TURNS OPEN
012345