COOLING PERFORMANCE DATA
GPC1436H41AB
5MM COILS
MODEL: GPC1436H41A*
EXPANDED PERFORMANCE DATA
COOLING OPERATION
Outdoor Ambient Temperature
65 75 85 95 105 115
Entering Indoor Wet Bulb Temperature
IDB*Airflow 59636771596367715963677159 63 67 715963677159636771
MBh 35.8 37.1 40.7 - 35.0 36.3 39.8 - 34.2 35.4 38.8 - 33.3 34.6 37.9 - 31.7 32.8 36.0 - 29.3 30.4 33.3 -
S/T 0.74 0.62 0.43 - 0.77 0.64 0.45 - 0.79 0.66 0.46 - 0.82 0.68 0.47 - 0.85 0.71 0.49 - 0.85 0.71 0.49 -
Delta T181612 - 181612 - 181612 - 19 16 12 - 181612 - 171511 -
1350 KW 2.37 2.42 2.50 - 2.56 2.61 2.70 - 2.72 2.78 2.87 - 2.86 2.93 3.02 - 2.98 3.05 3.15 - 3.09 3.16 3.26 -
AMPS 10.3 10.5 10.8 - 11.0 11.2 11.5 - 11.8 12.0 12.4 - 12.5 12.8 13.2 - 13.2 13.5 13.9 - 13.9 14.2 14.7 -
HI PR 236 254 268 - 265 285 301 - 301 324 342 - 343 369 390 - 386 415 439 - 426 459 485 -
LO PR 110 117 128 - 117 124 135 - 121 129 141 - 127 135 148 - 133 142 155 - 138 147 160 -
MBh 34.8 36.1 39.5 - 34.0 35.2 38.6 - 33.2 34.4 37.7 - 32.4 33.5 36.8 - 30.7 31.9 34.9 - 28.5 29.5 32.3 -
S/T 0.71 0.59 0.41 - 0.73 0.61 0.43 - 0.75 0.63 0.44 - 0.78 0.65 0.45 - 0.81 0.67 0.47 - 0.81 0.68 0.47 -
Delta T191612 - 191713 - 191713 - 19 17 13 - 191612 - 181512 -
70 1201 KW 2.35 2.40 2.48 - 2.54 2.59 2.67 - 2.70 2.76 2.85 - 2.84 2.90 3.00 - 2.96 3.02 3.13 - 3.06 3.13 3.24 -
AMPS 10.2 10.4 10.7 - 10.9 11.1 11.4 - 11.7 11.9 12.3 - 12.4 12.7 13.1 - 13.1 13.4 13.8 - 13.8 14.1 14.5 -
HI PR 234 251 266 - 262 282 298 - 298 321 339 - 340 365 386 - 382 411 434 - 422 454 480 -
LO PR 109 116 127 - 115 123 134 - 120 128 139 - 126 134 146 - 132 141 153 - 137 145 159 -
MBh 32.1 33.3 36.5 - 31.4 32.5 35.6 - 30.6 31.7 34.8 - 29.9 31.0 33.9 - 28.4 29.4 32.2 - 26.3 27.2 29.9 -
S/T 0.68 0.57 0.40 - 0.71 0.59 0.41 - 0.73 0.61 0.42 - 0.75 0.63 0.43 - 0.78 0.65 0.45 - 0.78 0.66 0.45 -
Delta T191713 - 191713 - 191713 - 20 17 13 - 191713 - 181612 -
1052 KW 2.30 2.35 2.42 - 2.47 2.53 2.61 - 2.63 2.69 2.77 - 2.77 2.83 2.92 - 2.88 2.95 3.05 - 2.98 3.05 3.15 -
AMPS 9.9 10.1 10.4 - 10.6 10.8 11.2 - 11.4 11.7 12.0 - 12.1 12.4 12.7 - 12.8 13.1 13.5 - 13.5 13.8 14.2 -
HI PR 227 244 258 - 254 274 289 - 289 311 329 - 329 355 374 - 371 399 421 - 409 441 465 -
LO PR 106 113 123 - 112 119 130 - 116 124 135 - 122 130 142 - 128 136 149 - 133 141 154 -
MBh 36.4 37.5 40.6 43.6 35.6 36.7 39.7 42.6 34.7 35.8 38.7 41.6 33.9
34.9
37.8 40.6 32.2 33.2 35.9 38.5 29.8 30.7 33.2 35.7
S/T 0.840.760.570.370.880.780.590.380.900.800.610.390.93
0.83
0.63 0.40 0.96 0.86 0.65 0.42 0.97 0.87 0.66 0.42
Delta T21191611212016112120161121
20
16 11 21 19 16 11 20 18 15 10
1350 KW 2.392.442.522.602.582.632.722.812.742.802.892.992.89
2.95
3.05 3.15 3.01 3.08 3.18 3.29 3.12 3.19 3.29 3.41
AMPS 10.3 10.5 10.8 11.2 11.1 11.3 11.6 12.0 11.9 12.1 12.5 12.9 12.6
12.9
13.3 13.7 13.3 13.6 14.0 14.5 14.0 14.4 14.8 15.3
HI PR 238 257 271 283 268 288 304 317 304 327 346 361 347
373
394 411 390 420 443 462 431 464 489 510
LO PR 111 119 129 138 118 125 137 146 122 130 142 151 129
137
149 159 135 143 157 167 139 148 162 172
MBh 35.4 36.4 39.4 42.3 34.6 35.6 38.5 41.3 33.7 34.7 37.6 40.4 32.9
33.9
36.7 39.4 31.3 32.2 34.8 37.4 29.0 29.8 32.3 34.6
S/T 0.810.720.550.350.840.750.570.360.860.770.580.370.88
0.79
0.60 0.38 0.92 0.82 0.62 0.40 0.93 0.83 0.63 0.40
Delta T22201611222017122220171222
21
17 12 22 20 17 11 21 19 15 11
75 1201 KW 2.372.422.502.582.562.612.702.792.722.782.872.972.86
2.93
3.02 3.12 2.98 3.05 3.15 3.26 3.09 3.16 3.27 3.38
AMPS 10.3 10.5 10.8 11.1 11.0 11.2 11.5 11.9 11.8 12.0 12.4 12.8 12.5
12.8
13.2 13.6 13.2 13.5 13.9 14.4 13.9 14.2 14.7 15.2
HI PR 236 254 268 280 265 285 301 314 301 324 342 357 343
369
390 407 386 415 439 457 426 459 485 505
LO PR 110 117 128 137 117 124 135 144 121 129 141 150 127
135
148 157 133 142 155 165 138 147 160 171
MBh 32.7 33.6 36.4 39.1 31.9 32.8 35.6 38.2 31.1 32.1 34.7 37.2 30.4
31.3
33.9 36.3 28.9 29.7 32.2 34.5 26.7 27.5 29.8 32.0
S/T 0.780.690.530.340.810.720.550.350.830.740.560.360.85
0.76
0.58 0.37 0.88 0.79 0.60 0.39 0.89 0.80 0.60 0.39
Delta T22201712222117122221171223
21
17 12 22 21 17 12 21 19 16 11
1052 KW 2.322.362.442.522.492.552.632.722.652.712.802.892.79
2.85
2.95 3.05 2.91 2.97 3.07 3.18 3.01 3.08 3.18 3.29
AMPS 10.0 10.2 10.5 10.8 10.7 10.9 11.2 11.6 11.5 11.8 12.1 12.5 12.2
12.5
12.8 13.3 12.9 13.2 13.6 14.0 13.6 13.9 14.3 14.8
HI PR 229 246 260 271 257 276 292 304 292 314 332 346 333
358
378 394 374 403 425 444 414 445 470 490
LO PR 107 114 124 132 113 120 131 140 118 125 137 145 123
131
143 153 129 138 150 160 134 142 155 166
* IDB: Entering Indoor Dry Bulb Temperature NOTE: Shaded area is ACCA (TVA) conditions