Goodman Mfg AVPTC313714 Air Conditioner User Manual


 
PRODUCT DESIGN
5
When this product is installed in the downflow installation in
an unconditioned space, remove the horizontal drain pan and
install the following insulation kit
AVPTC Model Insulation Kit
1830 DPI36-42/20
3137
4260
DPI48-61/-20
This kit is used to prevent sweating on the vertical drain pan.
To prevent the horizontal drain pan from sweating in high
humidity applications, it is recommended that a DPIH
insulation accessory kit be used. NOTE: The DPIH insu-
lation kit is not supplied with this product and must be
purchased separately.
See following chart for the correct DPIH kit.
AVPTC Model Insulation Kit
1830 DPIH36-42
3137
4260
DPIH48-61
*AVPTC is a multi-position, variable-speed air handler and is
used with R-410A. The unit's blower design includes a vari-
able-speed ECM motor and is compatible with heat pumps
and variable-capacity cooling applications. (See note below.)
*NOTE: Factory-sealed to achieve a 2% or less leakage rate
at 1.0" water gauge external duct static pressure.
Complies with the Factory-sealed Air Handling Credit as
listed in the 2001 Florida Building Code, Chapter 13, Section
610.2.A.2.1.