Glowworm Lighting 200 I Water Heater User Manual


 
13
2 Installation
TUNDISH
THERMOSTAT
MIXER
EXPANSION
VESSEL
HOT
WATER
CONNECTION
TEMPERATURE
AND PRESSURE
RELIEF VALVE
(95 °C, 7 BAR)
LEGIONNELLA
LOOP (optional)
FLOW
PUMP
BOILER
PRESSURE
LIMITING VALVE
(3.5 BAR)
WITH LINE
STRAINER
EXPANSION
RELIEF
VALVE
(6.0 BAR)
COLD
WATER
SUPPLY
FLUROCYL
DRAIN VALVE
MOTORISED
2 PORT VAVE
MOTORISED
2 PORT VAVE
RETURN
Diagram 2.3
14244
2.6 Mains water supply
The performance of unvented cylinders depends on the
available mains water pressure and the pipe size.
In order for the performance of the Flurocyl solar cylinder to
be ideal, an appropriate cold water supply must be available.
The measured static pressure must be at least 2.0 bar. A
corresponding ow rate of at least 20 - 25 l/min should be
available.
NOTE: The mains water pressure is reduced during periods of
high water consumption.Make sure you take measurements
during these periods.
Example: The available ow rate of mixed water at 40°C is 25
l/min (15 l/min hot water of 60°C from the solar cylinder mixed
with 10 l/min cold water of 10°C) if the measured static cold
mains water pressure is 2 bar.
The solar cylinder operates satisfactorily at a mains water
pressure of below 2 bar, but at a reduced ow rate.The
unvented solar cylinder should not be installed if the mains
water pressure is below 1 bar.You can obtain information on
alternative hot water supply systems from Glow-worm.
To keep the friction losses at a minimum, a minimum diameter
of 22mm is recommended for the cold water supply in the
building, satisfactory performances can also be achieved with
15mm pipes however.