Shut OFF utility power again. The generator
should start and the entire emergency load
should transfer to the generator.
Close the main breaker to restore utility power
and allow the engine to cool down and shut
itself OFF.
With the mode switch in AUTO, press the
EXERCISER switch. Hold it down for at least
10 seconds and release. The generator should
start within a few seconds. The unit will run
for about 12 minutes before shutting itself
down automatically.
Once set, the generator will exercise each week
at the same time. Be sure to show the owner
how to set the exercise function on the day and
time he/she wants the unit to exercise.
If the battery is ever disconnected for any reason,
the exercise function will have to be reset.
If your generator is equipped with the low
speed exercise feature, it was enabled at the
factory and no adjustment is needed.
As you can see, this installation is not difcult.
Simply follow all of the instructions that come
with the generator and observe all safety
procedures, applicable codes and regulations.
Setting The Automatic Exercise Function
17