Generac Power Systems OG 2697 Fan User Manual


 
14
Locate the transfer handle and insert the metal
end into the slot in the main contactor
assembly. Pull the handle DOWN to move the
main contacts to the standby power
(generator) position.
NEVER OPERATE THE TRANSFER
SWITCH MANUALLY WHEN LOADS
ARE CONNECTED.
Put the generator’s mode switch in MANUAL
to start the engine.
Allow the engine to warm up, then switch the
generator’s main breaker to the ON position.
The generator is now supplying electricity to
the transfer switch but is not carrying any load.
Check to be sure that voltage and frequency
from the generator is correct. If line-to-line
voltage is not 240 volts, refer to the Installation
Guide for the proper adjustment procedures. If
line-to-neutral voltage is not 120 volts, check
the neutral connection between the generator
and transfer switch.
When nished checking the voltage, switch the
generator’s main circuit breaker OFF and put
the mode switch in the OFF position to shut
down the generator.
Make sure the 2-pole circuit breaker you
installed in the main distribution panel is in the
OFF position.