FIGURE 1
MINIMUM OF 24” REQUIRED
FROM TOP OF UNIT TO CEILING.
INSIDE
WALL
MINIMUM OF 1”
SPACING REQUIRED
ON ALL SIDES OF
LINTELS
WSC SLEEVE
DRAIN
EXTENSION
THE UNIT.
7/8” MINIMUM
1” MINIMUM
3 1/2” FOR
SUBBASE
9/16” MINIMUM
OUTSIDE WALL
INSTALLATION INSTRUCTIONS
FOR “WSC” SLEEVE
MOUNTING HARDWARE PROVIDED
WALL PREPARATION:
STEP 1 The wall opening required for a “WSC” SLEEVE is 17 1/4” high by 27 1/4” wide.
STEP 2 LINTELS must be used in opening of brick veneer and masonry walls to support the material above the “WSC”
SLEEVE. The following considerations should also be given:
A. Adjustable SUB-BASE SB–89 or other unit support must be provided for panel wall type construction
and for walls less than 8” thick.
B. A minimum distance of 1” must be allowed on all sides of the unit to adjacent wall and  oor. Where the
sub–base is required, the minimum distance from the  oor to the sleeve must be 3 1/2”. To minimize
chances of short cycling of the compressor, the minimum clearance between the ceiling and the top of
the unit should be 24”. (See Figure 1).
ITEM
NO.
DESCRIPTION QTY.
1 SCREW, #12A X 2” 5