FMI FVFM27NR Gas Heater User Manual


 
www.fmiproducts.com
121353-01H6
REMOTE CONTROL ACCESSORIES
you classify your space and provide adequate
ventilation.

The air that leaks around doors and windows
may provide enough fresh air for combus-
tion and ventilation. However, in buildings of
unusually tight construction, you must provide
additional fresh air.

as construction where:
 -



-11

2

and
 
and
     
 





If your home meets all of the three criteria

See Ventilation Air From Outdoors
If your home does not meet all of the three
Determining Fresh-
Air Flow For Heater Location, 

The National Fuel Gas Code, ANSI Z223.1/
NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per
1,000 Btu/hr (4.8 m
3
per kw) of the aggregate
input rating of all appliances installed in that
space and an unconned space as a space
whose volume is not less than 50 cubic feet per
1,000 Btu/hr (4.8 m
3
per kw) of the aggregate
input rating of all appliances installed in that
space. Rooms communicating directly with the
space in which the appliances are installed*,
through openings not furnished with doors, are
considered a part of the unconned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation
grills between them.
There are 4 optional controls that can be pur-
chased separately for this log heater:
wall switch
wall thermostat
hand-held ON/OFF remote
hand-held thermostat remote
See Accessories, page 29.
Note: The wall thermostat or hand-held
thermostat may not be used where vented
decorative listing is required.
AIR FOR COMbUSTION AND VENTILATION
WARNING: This heater shall

    


National Fuel Gas Code, ANSI
Z223.1/NFPA 54, the International
Fuel Gas Code,  




Today’s homes are built more energy efcient
than ever. New materials, increased insula-
tion, and new construction methods help
reduce heat loss in homes. Home owners
weather strip and caulk around windows and
doors to keep the cold air out and the warm air
in. During heating months, home owners want
their homes as airtight as possible.
While it is good to make your home energy
efcient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning ap-
pliances need fresh air for proper combustion
and ventilation.
Exhaust fans, replaces, clothes dryers, and
fuel burning appliances draw air from the house
to operate. You must provide adequate fresh
air for these appliances. This will insure proper
venting of vented fuel-burning appliances.


The following are excerpts from National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 6 through 8 will help