Fedders R407C Air Conditioner User Manual


 
C5
PREPARATION OF PIPING
Pipe Length, Elevation and refrigerant charge
Cutting The Pipe And The Cables.
• Measure the distance between the
indoor and the outdoor units.
• Cut the pipe length about 10% more
than the measured distance.
• Cut the electrical cable with about 2
metres more than the measured dis-
tance.
• Each outdoor unit comes with a
refrigerant charge that is sufficient for
use with interconnecting tubing up to
7.5 metres.
• If the required interconnecting tube
exceeds 5 metres, for each additional
metre, add the amount of refrigerant
according to the table as shown below.
Max. Piping
Length per
Indoor Unit
Max. Elevation
per Indoor Unit
The recommended maximum allowable
tubing length between indoor and
outdoor is 15 metres.
The recommended maximum allowable
elevation between indoor and outdoor is
5 metres.
Liquid Pipe
Size
1/4”
Additional
Refrigerant
3/8”
21 g/m
57 g/m