England's Stove Works 12-FPL Stove User Manual


 
12
INSTALLATION
1. Remove all parts from inside the stove body. (If you purchased a leg unit, and it has the
factory packaging, remove the body of the stove from the shroud that it is attached to, referring
to Illustration 7 later in this manual. Those instructions detail how to exchange legs and
pedestal, but removal of the shroud is accomplished in the same manner).
2. Select the proper location for the stove. These appliances must not be installed any closer
than the minimum clearance to combustible materials shown in Illustration 1. The stove must
be installed on a non-combustible surface as shown in Illustration 1 and Illustration 2.
3. If non-combustible materials have been installed on the walls, obtain the minimum clearances
from either the manufacturer of these materials or the local building inspector’s office.
4. Install the stovepipe INSIDE the flue collar on the top of the stove, between the stove and the
chimney.
5. DO NOT use a grate to elevate the fire.
6. A clearance of 10.5” between single wall chimney connector and combustible materials is
required. Check with authorities having jurisdiction in your area with any questions.
7. All pipe sections must be connected with the male (crimped) end toward the stove.
8. Fasten the stove pipe to the flue collar by the use of three sheet metal screws. Do the same
at each additional joint to make the entire installation rigid.
9. Maintain the required diameter flue for the entire installation.
10. If you are connecting the stove to an old masonry flue, be sure to have it inspected for cracks
and general condition. Relining with a stainless steel liner may be required.
11. It is recommended that no more than two 90-degree bends be used in the stovepipe
installation. More than two 90-degree bends may decrease the amount of draw, and possibly
cause smoke spillage.
12. This unit has a factory-installed damper. Do not install or use additional dampers with this
unit.
13. Single wall flue pipe assemblies must not exceed 10 feet in overall length.
FAILURE TO FOLLOW THE MINIMUM CLEARANCE REQUIREMENTS MAY RESULT IN
AN UNSAFE INSTALLATION.