EMI UNH-T2H-T3H-T4H Heat Pump User Manual


 
Rome, New York, USAEnviromaster International LLC
5
INTERCONNECTING TUBING SPECIFICATIONS
Indoor
Unit
Outdoor
Circuit
Capacity
Maximum Separation,
Equivalent ft (m)
Maximum Elevation
Difference
ft (m)
Liquid
Line OD
Suction
Line OD
Condensate
Line ID
UNH09 9,000 Btuh 100 (30.5) 35 (10.7) 1/4” 1/2” 1/2”
UNH12 12,000 Btuh 100 (30.5) 35 (10.7) 1/4” 1/2” 1/2”
UNH24 18,000 Btuh 100 (30.5) 35 (10.7) 3/8” 5/8”* 1/2”
UNH24 24,000 Btuh 100 (30.5) 35 (10.7) 3/8” 3/4” 1/2”
* UNH24 Suction Connection size is 3/4” O.D. and must bush down at the UNH Unit.
Manufacturer reserves the right to change these specications at any time without incurring obligation.
INDOOR AIR FLOW
Indoor Unit
CFM (l/s)
Coil ft/min (m/s) Air Throw, ft. (m)
High Speed Low Speed
UNH09
or
UNH12
425 (200) 375 (175)
Dry
900 (4.6) 15 (4.6)
UNH
24 700 (350) 550 (250) 1,225 (6.2) 24 (7.3)
SOUND DATA
Unit Sound dBA
UNH09 or UNH12 51
UNH24 56
T2H 70
T3H 70
T4H 70
Note: Sound data for indoor unit at high speed, 230 V
Sound data for outdoor unit at 230V
WEIGHT DATA
Unit Weight, lbs (kg)
UNH09 92 (41.8)
UNH12 95 (43.2)
UNH24 116 (52.7)
T2H 325 (147.7)
T3H 325 (147.7)
T4H 325 (147.7)
EMI ENGINEERING SUBMITTAL UNH-T2H-T3H-T4H
Outdoor
Unit
Power Supply
V-1-60
Control*
V-1-60
Compressor Outdoor Fan Motor
Unit
FLA
MCA MOCP
Volts Min Max Qty RLA LRA Qty FLA Hp
T3H2240
208/230 197 240 24
2 4.3 27.0
1 1.8 0.33 19.2 21.4 30
1
8.8 54.0
T3H2220
208/230 197 240 24 3 4.3 27.0 1 1.8 0.33
14.7 15.8 20
T4H9999
208/230 197 240 24 4 3.4 23.0 1 1.8 0.33 15.4 16.3 20
T4H9992
208/230 197 240 24
3 3.4 23.0
1 1.8 0.33 16.3 17.4 20
1
4.3 27.0
T4H9922
208/230 197 240 24
2 3.4 23.0
1 1.8 0.33 17.2 18.3 20
2
4.3 27.0
T4H9222
208/230 197 240 24
1 3.4 23.0
1 1.8 0.33 18.1 19.2 20
3
4.3 27.0
T4H2222
208/230 197 240 24 4 4.3 27.0 1 1.8 0.33 19.0 20.1 25
Note: * - Control Voltage is supplied from the indoor unit. No separate supply required.
ELECTRICAL SPECIFICATIONS Continued