Multi-zone Heat Pump Condensing Units
T2HA DIMENSIONS AND SPECIFICATIONS
NOTE: All EMI products are subject to ongoing development programs so design and
specifications may change without notice.
SOUND & WEIGHT DATA
Model
Sound Weight
dBA Lbs.
T2HA8800 70 325
T2HA8400 70 325
T2HA4400 70 325
INTERCONNECTING TUBING SPECS
T2HA, T3HA, & T4HA models:
Nominal
Circuit
Capacity
Maximum
Length
Maximum
Lift
Liquid
Line
OD
Suction
Line
OD
9,000 100’ 35’ 1/4” 1/2”
12,000 100’ 35’ 1/4” 1/2”
18,000 100’ 35’ 3/8” 5/8”
24,000 100’ 35’ 3/8” 3/4”
T2HA, T3HA, AND T4HA - 208/230V - 60 HERTZ 1 - PHASE
CAPACITY
FAN MTR
COMPRESSOR
TOTAL
AMPS
MCA
HACR
BRKR
MIN
VOLT
AMPS HP
CIRCUIT #1 CIRCUIT #2 CIRCUIT #3 CIRCUIT #4
RLA LRA RLA LRA RLA LRA RLA LRA
8800 1.8 0.33 5.4 36.0 5.4 36.0 - - - - 12.6 14.0 15.0 197
4400 1.8 0.33 8.8 54.0 8.8 54.0 - - - - 19.4 21.6 30.0 197
8400 1.8 0.33 5.4 36.0 8.8 54.0 - - - - 16.0 18.2 25.0 197
Circuit Designators: 9 = 9000 Btuh 2 = 12000 Btuh 8 = 18000 Btuh 4 = 24000 Btuh (ex. - 8400 consists of one 18000 Btuh
compressor and one 24000 Btuh compressor)