Hardware Installation (Cont.)
4 AUX Power Wiring
The control panel can provide a maximum of 550mA of current for modules, powered detectors, relays, LED’s etc.… If the total current
required exceeds 550mA an additional power supply is required (e.g.,PC5200, PC5204). See list below.
NOTE: Min/max operating voltages for devices, sensors and modules is 9.5V
DC - 14VDC
Refer to the list of Compatible Devices on the first page for the current draw of individual devices
5 PGM Wiring
PGMs switch to ground when activated by control panel.
Connect the positive side of the device to be activated to the AUX+
Terminal. Connect the negative terminal to the PGM.
current output is as follows
• PGM 1, 3, 4 .................... 50mA
• PGM 2 .......................... 300mA
For currents levels greater than 300mA a relay is required.
PGM2 can also be used for 2-wire smoke detectors.
NOTE: Use SEOL resistors on Fire Zones ONLY.
PGM 1, LED Output with current limiting resistor and Optional Relay
driver output
2-wire Smoke Detectors Initiating Circuit
• Style B (Class B), Supervised, Power Limited
• Compatibility Identifier ........................................................ PC18-1
• DC Output Voltage.....................................................9.8-13.8 VDC
• Detector Load .............................................................2 mA (MAX)
• Single-end-of-line (SEOL) Resistor ..................................... 2200Ω
• Loop Resistance............................................................24Ω (MAX)
• Standby Impedance.................................................. 1020Ω (ΝΟΜ)
• Alarm Impedance ........................................................570Ω (MAX)
• Alarm Current............................................................89 mA (MAX)
Compatibility ID For FSA-210B Series is: FSA200 4-wire Smoke Detectors
6 Telephone Line Wiring
Wire the telephone connection terminals (TIP, Ring, T-1, R-1) to an
RJ-31x Connector as indicated.
For connection of multiple devices to the telephone line, wire in the
sequence indicated.
Telephone format is programmed in section [350].
Telephone Call Directions are programmed in section [351]-[376].
7 G ro u nd 8 Ba t te r y 9 A C W ir i ng
Ground Installation A sealed, rechargeable, lead
acid battery or gel type battery is
required to meet UL require-
ments for power standby times.
NOTE: UL Residential/Commer-
cial Burglary installations require
4Hrs Power Standby time.
NOTE: UL/ULC Residential Fire
& Home Care installations
require 24 Hr power standby.
ULC Commercial Burglary
and Fire monitoring installations
require 24 Hr power standby.
Standby Battery Guide
Battery Charging Current: 400 mA
Batt Standby
Size 4Hr 24Hr
-------------------------------------------------
4Ahr 550mA ----
7Ahr 550mA 190mA
14Ahr 550mA 480mA
NOTE:
Replace batteries every 3-5 years.
Battery capacity will deteriorate with
age and number of charge/discharge
cycles
AC Wiring
UL Listed Installations
Primary: 120VAC/60Hz./0.33A
Secondary: 16.5VAC/40VA
DSCPTD 1640 Plug-in, Class 2
Transformer.
NOTE: Do not connect trans-
former to a receptacle controlled
by a switch. (UL Listed Installations
Only)
1 PGM 2
AUX
1 PGM 2 1 PGM 2
RED
BLK
DSC
RM-1
WHT YEL GRN
COM N.C. N.O.
AUX
AUX
NOTE:
SMOKE
DETECTOR
POWER
12 V
DC
ALARM
INITIATING
LOOP
RESISTANCE
100
Ω
RM-1 POWER LOOP
SUPERVISORY RELAY
RED
WHT
WHT
GRN
IN
COM
NO
ALM
IN
OUT
OUT
BLK
Refer to Installation Manual and
Smoke Detector Instruction Sheet
when positioning detectors.
Compatible 2-wire
Smoke Detector
DSC FSA-210B Series
FSA-210B
FSA-210BT
FSA-210BS
FSA-210BST
FSA-210BLST
FSA-210BR
FSA-210BRT
FSA-210BRS
FSA-210BRST
FSA-210BLRST
Compatible 4-wire
Smoke Detector
DSC FSA-410B Series
FSA-410B
FSA-410BT
FSA-410BS
FSA-410BST
FSA-410BLST
FSA-410BR
FSA-410BRT
FSA-410BRS
FSA-410BRST
FSA-410BLRST
35mA
max.
Smoke Detector must be latching type (e.g., DSC FSA 410B Series)
To reset smoke detector, Enter 7 2
[][] []
✱
1 PGM 2
AUX
NOTE NOT
: Do combine models from different Manufacturers
On the same circuit. Operation may be impaired.
2200
Ω
END-OF-LINE
RESISTOR
EOLR-3
1 PGM 2
AUX
Tighten nut to break paint
and make a good
connection to the cabinet
Nut
Star washer
Lock washer
Lock washer
Ground wire
from building
electrical
installation
Earth ground
connection
Nut
Cabinet
Bolt
WWW.DIYALARMFORUM.COM