12 Equipment Data
1 Type and order code
SI 24TE SI 37TE
2Design
2.1 Degree of protection according to EN 60 529 IP 21 IP 21
2.2 Installation location Indoors Indoors
3 Performance data
3.1 Operating temperature limits:
Heating water flow °C up to 60 up to 60
Brine (heat source) °C -5 to +25 -5 to +25
Antifreeze Monoethylene glycol Monoethylene glycol
Minimum brine concentration (-13 °C freezing temperature) 25% 25%
3.2 Temperature spread of heating water (flow/return flow) at B0 / W35K 9.4 5.0 9.8 5.0
3.3 Heat output / COP at B-5 / W55
1
kW / ---
2
1. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, both the bivalence point and the regulation should
also be taken into consideration. The specified values, e.g. B10 / W55, have the following meaning: Heat source temperature 10 °C and heating water flow temperature 55 °C.
2. Operation with 2 compressor
19.7 / 2.3 28.9 / 2.4
kW / ---
3
3. Operation with 1 compressors
9.3 / 2.1 12.1 / 2.2
at B0 / W45
1
kW / ---
2
22.3 / 3.1 33.0 / 3.3
kW / ---
3
11.3 / 3.1 13.4 / 2.8
at B0 / W50
1
kW / ---
2
22.7 / 2.9 34.3 / 3.1
kW / ---
3
10.8 / 2.7 13.1 / 2.4
at B0 / W35
1
kW / ---
2
24.0 / 4.3 23.7 / 4.1 37.2 / 4.6 35.4 / 4.3
kW / ---
3
12.5 / 4.4 12.7 / 4.3 17.0 / 4.2 18.3 / 4.5
3.4 Sound power level dB(A)
3.5 Sound pressure level at a distance of 1 m dB(A)
3.6 Heating water flow with an internal pressure differential of m³/h / Pa 2.2 / 3100 4.0 / 9800 3.2 / 1650 6.0 / 5100
3.7 Brine throughput with an internal pressure differential (heat source) of
m³/h / Pa
5.6 / 13000 5.6 / 13000 8.5 / 10000 8.5 / 10000
3.8 Refrigerant; total filling weight type / kg R404A / 3.7 R404A / 6.8
4 Dimensions, connections and weight
4.1 Device dimensions without connections
4
H x W x L mm
4. Note that additional space is required for pipe connections, operation and maintenance.
1660 x 1000 x 775 1660 x 1000 x 775
4.2 Device connections to heating system Inch G 1 1/4'' internal/external G 1 1/4'' internal/external
4.3 Device connections to heat source Inch G 1 1/2'' internal/external G 2'' internal/external
4.4 Weight of the transportable unit(s) incl. packing kg 282 371
5 Electrical connection
5.1 Nominal voltage; fuse protection V / A 400 / 20 400 / 20
5.2 Nominal power consumption
1
B0 W35 kW
5.61 5.81 7.96 8.17
5.3 Starting current with soft starter A 20 26
5.4 Nominal current B0 W35 / cos ϕ
2
A / ---
10.12 / 0.8 10.48 / 0.8 14.40 / 0.8 14.92 / 0.8
6 Complies with the European safety regulations
5
5. See CE declaration of conformity
5
7 Additional model features
7.1 Water in device protected against freezing
6
6. The heat circulating pump and the heat pump controller must always be ready for operation.
Yes Yes
7.2 Performance levels 2 2
7.3 Controller internal/external Internal Internal