AIR FOR COMBUSTION
AND VENTILATION
Continued
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION


Use this work sheet to determine if you have a
conned or unconned space.
 Includes the room in which you will
install heater plus any adjoining rooms with door-
less passageways or ventilation grills between
the rooms.
1. Determine the volume of the space (length x
width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 22 ft. (length) x 18 ft.
(width) x 8 ft. (ceiling height) = 3168 cu. ft.
(volume of space)
If additional ventilation to adjoining room is
supplied with grills or openings, add the volume
of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 3168 cu. ft. (volume of space) x 20 =
63,360 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in
the space.
Vent-free replace ___________ Btu/Hr
Gas water heater* ___________ Btu/Hr
Gas furnace ___________ Btu/Hr
Vented gas heater ___________ Btu/Hr
Gas replace logs ___________ Btu/Hr
Other gas appliances* + __________ Btu/Hr
Total = __________ Btu/Hr
* Do not include direct-vent gas appliances. Di-
rect-vent draws combustion air from the outdoors
and vents to the outdoors.
Example:
Gas water heater __________ Btu/Hr
Vent-free replace + ________ Btu/Hr
Total = ________ Btu/Hr
4. Compare the maximum Btu/Hr the space can
support with the actual amount of Btu/Hr used.
_________
Btu/Hr (maximum the space can support)
_________
Btu/Hr (actual amount of Btu/Hr used)
Example: 63,360 Btu/Hr (maximum the space
can support)
79,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the above example is a conned space
because the actual Btu/Hr used is more than the maxi-
mum Btu/Hr the space can support. You must provide
additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoin-
ing room. If the extra space provides an unconned
space, remove door to adjoining room or add
ventilation grills between rooms. See Ventilation
Air From Inside Building, page 9.
B. Vent room directly to the outdoors. See Ventila-
tion Air From Outdoors, page 9.
C. Install a lower Btu/Hr replace, if lower Btu/Hr
size makes room unconned.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is
an unconned space. You will need no additional
fresh air ventilation.
WARNING: If the area in which
   
    
     
    



in the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 Section 5.3

40,000
39,000
79,000