Desa VN30BTA Electric Heater User Manual


 
www.desatech.com
113061-01F18
POSSIBLE CAUSE
1. Control knob not fully
pressed in
2. Control knob not pressed in
long enough
3. Safety interlock system has
been triggered
4. Equipment shutoff valve not
fully open
5. Thermocouple connection
loose at control valve
6. Pilot flame not touching
thermocouple, which allows
thermocouple to cool, caus-
ing pilot ame to go out. This
problem could be caused by
one or both of the following:
A) Low gas pressure
B) Dirty or partially clogged
ODS/pilot
7. Thermocouple damaged
8. Control valve damaged
1. Burner orice is clogged
2. Inlet gas pressure is too low
1. Manifold pressure is too
low
2. Burner orice is clogged
1. Burner orice is clogged or
damaged
2. Burner damaged
3. Gas regulator defective
OBSERVED PROBLEM
ODS/pilot lights but flame
goes out when control knob is
released
Burner does not light after ODS/
pilot is lit
Delayed ignition of burner
Burner backring during
combustion
REMEDY
1. Press in control knob fully
2. After ODS/pilot lights, keep con-
trol knob pressed in 30 seconds
3. Wait one minute for safety in-
terlock system to reset. Repeat
ignition operation
4. Fully open equipment shutoff
valve
5. Hand tighten until snug, then
tighten 1/4 turn more
6. A) Contact local natural or
propane/LP gas company
B) Clean ODS/pilot (see
Cleaning and Maintenance,
page 16) or replace ODS/pilot
assembly
7. Replace pilot assembly
8. Replace control valve
1. Clean burner (see Cleaning
and Maintenance, page 16) or
replace burner orice
2. Contact local natural or pro-
pane/LP gas company
1. Contact local natural or pro-
pane/LP gas company
2. Clean burner (see Cleaning
and Maintenance, page 16) or
replace burner orice
1. Clean burner (see Cleaning
and Maintenance, page 16) or
replace burner orice
2. Replace burner
3. Replace gas regulator
TROUBLESHOOTING
Continued