Desa VM42(B,H) Indoor Fireplace User Manual


 
www.desatech.com
108795-01V 9
INSTALLING TRANSITION PIPE AND
STARTER COLLAR
The transition pipe and starter collar shown
in Figure 9 are supplied with the replace,
unattached and ready for installation. Re-
move starter collar and set aside. Slide
transition pipe over vent collar and attach
with a minimum of three screws. Replace
starter collar over transition pipe and attach
using four screws located on leg stands (ve
used on model M42). To install B-vent piping,
slide the rst piece of B-vent over transition
pipe and attach with either a minimum of two
screws or other means approved by the vent
manufacturer.
Figure 9 - Installing Transition Pipe and
Starter Collar
B-Vent Piping
Transition Pipe
Starter Collar
Vent Collar
PRE-INSTALLATION PREPARATION
Continued
VENTING INSTALLATION
60° or greater. The total vertical height in this
example represents the minimum height of 8
feet and therefore the allowable lateral is 6
feet when the 75% rule applies. If the lateral
length must exceed 75% then the system
must be sized in accordance with Category I
venting tables.
Example2: Shows a multiple offset each at
45° of inclination. Multiple offsets are permit-
ted if they do not exceed 45° of inclination. The
total lengths of the two offsets are not required
to meet the 75% allowable rule.
Example3:Shows a single offset at 45° of
inclination and therefore the lateral length at
10 feet of offset does not have to meet the
75% rule.
In each case the offsets must be supported
and restops must be positioned wherever
the vent must pass through a sub-oor, ceil-
ing joist or an attic overhang. The vent pipe
must terminate vertically into a listed type vent
cap and extend a sufcient height through
an approved roof ashing, roof jack or a roof
thimble. At all points listed clearances must
be maintained.
Vent terminations must be located in ac-
cordance with height and proximity rules of
NFPA No. 54. These rules apply to vents at
12" diameter or less and require a minimum
height in accordance with the roof pitch and a
minimum of 8 ft. distance from a vertical wall
or obstruction (see Figure 11, page 10).
A B-type venting system must be connected
to the appliance for venting to the outside of
the building.
The following section is provided as a guide
to a standard B-type vent installation.
Standing codes requirements concerning B-
type vent installations may vary within your
state, province or local codes jurisdiction.
Therefore, it is recommended that you check
with your local building codes for specic
requirements or in absence of local codes,
follow Section 7.0 of the current National Fuel
Gas Code ANSI Z223.1/NFPA 54.
This gas appliance must be vented to the
outdoors only and may not be terminated into
an attic space or into a chimney ue servicing
a solid fuel burning appliance.
This appliance may be vented through a
manufactured chimney system or a masonry
chimney using a B-vent adapter or a chim-
ney liner system if all are listed, inspected
and approved by local codes and/or building
authorities.
The examples shown in Figure 10, page 10
are typical of most B-vent installations and
codes practices.
Example1: Shows the minimum allowable
system height and lateral offset for a 60° or
greater inclination. Code species that offsets
at 60° or greater are considered horizontal
and must follow the 75% rule for lateral to
total vertical system height. Codes also allow
only one offset in the total system when at