Desa Unvented Propane Gas Log Heater Model Split Oak and American Oak Design Indoor Fireplace User Manual


 
10
103427
UNVENTED PROPANE GAS LOG HEATER
Tee Joint
Pipe
Nipple
Cap
3" Minimum
Sediment
Trap
Gas
Regulator
From External
Regulator
(11" W.C.** to
14" W.C. Pressure)
A.G.A. Design-Certified
Manual Shutoff Valve With
1/8" NPT Tap*
Approved Flexible Gas
Hose (if allowed by local
codes)
CAUTION: Avoid damage to
regulator. Hold gas regulator with
wrench when connecting it to gas
piping and/or fittings.
Figure 15 - Gas Connection
* Purchase the optional A.G.A. design-certified manual shutoff valve from your dealer. See
Accessories, page 23.
** Minimum inlet pressure for purpose of input adjustment.
The installer must supply an external regu-
lator. The external regulator will reduce
incoming gas pressure. You must reduce
incoming gas pressure to between 11 and 14
inches of water. If you do not reduce incom-
ing gas pressure, heater regulator damage
could occur. Install external regulator with
the vent pointing down as shown in Figure
14. Pointing the vent down protects it from
freezing rain or sleet.
Figure 14 - External Regulator With Vent
Pointing Down
Propane
Supply
Tank
External
Regulator
Vent
Pointing
Down
WARNING: Never connect
heater to private (non-utility) gas
wells. This gas is commonly
known as wellhead gas.
Installation must include a manual shutoff
valve, union, and plugged 1/8" NPT tap.
Locate NPT tap within reach for test gauge
hook up. NPT tap must be upstream from
heater (see Figure 15).
Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged heater valves.
CAUTION: Use only new,
black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of 1/2"
diameter or greater to allow
proper gas volume to heater. If
pipe is too small, undue loss of
pressure will occur.
Install sediment trap in supply line as shown
in Figure 15. Locate sediment trap where it
is within reach for cleaning. Locate sedi-
ment trap where trapped matter is not likely
to freeze. A sediment trap traps moisture
and contaminants. This keeps them from
going into heater controls. If sediment trap
is not installed or is installed wrong, heater
may not run properly.
CAUTION: Use pipe joint seal-
ant that is resistant to liquid pe-
troleum (LP) gas.
INSTALLATION
Continued
CONNECTING TO GAS
SUPPLY
NOTICE: A qualified service per-
son must connect heater to gas
supply. Follow all local codes.
CAUTION: Never connect
heater directly to the propane
supply. This heater requires an
external regulator (not supplied).
Install the external regulator be-
tween the heater and propane
supply.
Installation Items Needed
Before installing heater, make sure you have
the items listed below.
external regulator (supplied by installer,
see below)
piping (check local codes)
sealant (resistant to LP gas)
manual shutoff valve *
test gauge connection *
sediment trap
tee joint
pipe wrench
* An A.G.A. design-certified manual shutoff
valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Pur-
chase the optional A.G.A. design-certified
manual shutoff valve from your dealer. See
Accessories, page 23.
Continued