7
100165
WARNING ICON G 001
WARNING
Never use an open flame to check for a leak. Apply a mixture
of liquid soap and water to all joints. Bubbles forming show a
leak. Correct all leaks at once.
WARNING ICON G 001
WARNING
Do not adjust regulator below 48 kPa (7 psig) or above 138
kPa (20 psig). Heater may not run properly.
Figure 4 - Hose and Inlet Connector
Hose
3. Connect hose to inlet connector. Tighten firmly using a wrench.
IMPORTANT:
Use extra hose or piping if needed. Install extra hose or piping
between hose/regulator assembly and propane tank. You must use the regula-
tor supplied with heater.
7. Close propane supply valve.
6. Check all connections for leaks.
Figure 5 - Adjustable Regulator Set At 48 kPa (7 psig)
I
N
C
R
E
A
S
E
1
0
1
5
2
0
10
15
20
5
5
5
10
15
20
Regulator
4. Open propane supply valve on propane tank(s) slowly.
Note:
If not opened
slowly, excess-flow check valve on propane tank will stop gas flow. If this
happens, close propane supply valve and open again slowly.
5. Adjust regulator between 48 and 138 kPa (7 and 20 psig) (see Figure 5).
Note:
Higher regulator setting will allow heater to produce more heat.
INSTALLATION
Continued
Inlet Connector