Desa PH70EDI Air Conditioner User Manual


 
7
099800
VENTILATION
OPERATION
Continued
Figure 6 - Flame-Out Control Reset
Button, 30/70,000 BTU/Hr Models
Figure 7 - Flame-Out Control Reset
Button, 90,000 BTU/Hr Model
!
WARNING
Follow the minimum fresh, outside air ventilation
requirements. If proper fresh, outside air ventilation is not
provided, carbon monoxide poisoning can occur. Provide
proper fresh, outside air ventilation before running heater.
Provide a fresh air opening of at least 2800 square cm for each 100,000 BTU/Hr
rating. Provide extra fresh air if more heaters are being used.
Example:
A 150,000 BTU/Hr heater requires one of the following:
a two-car garage door raised 15.24 cm
a single-car garage door raised 22.86 cm
two, 76.20 cm windows raised 30.48 cm
Flame-Out
Control
Reset
Button
!
WARNING
Review and understand the warnings in the Safety
Information Section. They are needed to safely operate this
heater. Follow all local codes when using this heater.
To Start Heater
1. Follow all ventilation and safety information.
2. Fill fuel tank with kerosene or No. 1 fuel oil.
3. Attach fuel cap.
4. Plug power cord of heater into standard 230 volt/50 hertz, grounded (earthed)
outlet. Use an extension cord if needed. Use only a three-wire, grounded
(earthed) extension cord.
Extension Cord Wire Size Requirements
Up to 30.5 meters long, use 16 AWG (1.0 mm
2
) conductor
30.6 to 61 meters long, use 14 AWG (1.5 mm
2
) conductor
Heater will start when power cord is plugged into outlet. If not, push in flame-
out control reset button (see Figures 6 thru 8).
Flame-
Out
Control
Reset
Button