Desa LSL3124P Electric Heater User Manual


 
www.desatech.com
111347-01E
6
AIR FOR COMBUSTION
AND VENTILATION
Continued
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion and
ventilation. However, in buildings of unusually
tight construction, you must provide additional
fresh air.
Unusually tight construction is defined as
construction where:
a. walls and ceilings exposed to the out
-
side atmosphere have a continuous
water vapor retarder with a rating of one
perm (6 x 10
-11
kg per pa-sec-m
2
) or less
with openings gasketed or sealed and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to areas
such as joints around window and door
frames, between sole plates and floors,
between wall-ceiling joints, between
wall panels, at penetrations for plumb
-
ing, electrical and gas lines and at other
openings.
If your home meets all of the three criteria
above, you must provide additional fresh
air. See Ventilation Air From Outdoors
,
page 7.
If your home does not meet all of the three
criteria above, proceed to Determining
Fresh-Air Flow For Heater Location.
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA
54 defines a confined space as a space whose
volume is less than 50 cubic feet per 1,000 Btu
per hour (4.8 m
3
per kw) of the aggregate input
rating of all appliances installed in that space and
an unconfined space as a space whose volume is
not less than 50 cubic feet per 1,000 Btu per hour
(4.8 m
3
per kw) of the aggregate input rating of
all appliances installed in that space. Rooms com-
municating directly with the space in which the
appliances are installed*, through openings not
furnished with doors, are considered a part of the
unconfined space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation grills
between them.
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION
Determining if You Have a Confined or
Unconfined Space
Use this work sheet to determine if you have a
confined or unconfined space.
Space: Includes the room in which you will install
heater plus any adjoining rooms with doorless
passageways or ventilation grills between the
rooms.
1. Determine the volume of the space (length x
width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft.
(volume of space)
If additional ventilation to adjoining room is
supplied with grills or openings, add the volume
of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) x 20 =
51,200 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in
the space.
Vent-free heater ___________
Btu/Hr
Gas water heater* ___________
Btu/Hr
Gas furnace ___________
Btu/Hr
Vented gas heater ___________
Btu/Hr
Gas fireplace logs ___________
Btu/Hr
Other gas appliances* + __________
Btu/Hr
Total = __________
Btu/Hr
* Do not include direct-vent gas appliances. Di
-
rect-vent draws combustion air from the outdoors
and vents to the outdoors.
Example:
Gas water heater
__________ Btu/Hr
Vent-free fireplace + ________
Btu/Hr
Total = ________
Btu/Hr
4. Compare the maximum Btu/Hr the space can
support with the actual amount of Btu/Hr used.
_________
Btu/Hr (maximum the space can support)
_________
Btu/Hr (actual amount of Btu/Hr used)
Example: 51,200 Btu/Hr (maximum the space
can support)
73,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the above example is a confined
space because the actual Btu/Hr used is more than
the maximum Btu/Hr the space can support. You
40,000
33,000
73,000