Desa LDL3924PR Electric Heater User Manual


 
111515-01C
For more information, visit www.desatech.com
For more information, visit www.desatech.com
12
Pipe Nipple Cap Tee Joint
* Purchase the optional CSA design-certified equipment shutoff valve
from your dealer. See Accessories, page 27.
** Minimum inlet pressure for purpose of input adjustment.
Figure 16 - Gas Connection
Gas
Control
3" Minimum
Sediment Trap
PROPANE/LP-
From External
Regulator
(11" W.C.** to 14"
W.C. Pressure)
NATURAL-
From Gas Meter
(5" W.C.** to 10.5"
W.C. Pressure)
CSA Design-Certified
Equipment Shutoff Valve
With 1/8" NPT Tap*
Approved Flexible Gas Hose
(if allowed by local codes)
Propane/LP
Supply Tank
External Regulator
INSTALLATION
Continued
Figure 15 - External Regulator With Vent Pointing Down
Vent
Pointing
Down
IMPORTANT:
Install equipment shutoff valve in an accessible
location. The equipment shutoff valve is for turning on or shutting
off the gas to the appliance.
Check your building codes for any special requirements for locating
equipment shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male NPT threads. This will
prevent excess sealant from going into pipe. Excess sealant in pipe
could result in clogged heater valves.
WARNING: Use pipe joint sealant that is resistant
to liquid petroleum (LP) gas.
We recommend that you install a sediment trap in supply line as
shown in Figure 16. Locate sediment trap where it is within reach for
cleaning. Install in piping system between fuel supply and heater.
Locate sediment trap where trapped matter is not likely to freeze. A
sediment trap traps moisture and contaminants. This keeps them
from going into heater controls. If sediment trap is not installed or
is installed wrong, heater may not run properly.
CAUTION: Avoid damage to gas control. Hold gas
fitting with wrench when connecting it to gas piping
and/or fittings.
INSTALLATION
Connecting To Gas Supply
CONNECTING TO GAS SUPPLY
WARNING: This appliance requires a 1/2" NPT
(National Pipe Thread) inlet connection to the pres-
sure regulator.
WARNING: A qualified service person must con-
nect heater to gas supply. Follow all local codes.
CAUTION: Never connect propane/LP fireplace
directly to the propane/LP supply. This heater requires
an external regulator (not supplied). Install the external
regulator between the heater and propane/LP supply.
WARNING: Never connect natural gas fireplace to
private (non-utility) gas wells. This gas is commonly
known as wellhead gas.
Installation Items Needed
Before installing heater, make sure you have the items listed below.
external regulator (supplied by installer)
piping (check local codes)
sealant (resistant to propane/LP gas)
equipment shutoff valve *
test gauge connection *
sediment trap
tee joint
pipe wrench
* A CSA design-certified equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge connection. Purchase
the optional CSA design-certified equipment shutoff valve from
your dealer. See Accessories, page 27.
For propane/LP units, the installer must supply an external regula-
tor. The external regulator will reduce incoming gas pressure. You
must reduce incoming gas pressure to between 11 and 14 inches of
water. If you do not reduce incoming gas pressure, heater regulator
damage could occur. Install external regulator with the vent point-
ing down as shown in Figure 15. Pointing the vent down protects it
from freezing rain or sleet.
CAUTION: Use only new, black iron or steel pipe.
Internally-tinned copper tubing may be used in certain
areas. Check your local codes. Use pipe of 1/2" diam-
eter or greater to allow proper gas volume to heater. If
pipe is too small, undue loss of volume will occur.
Installation must include an equipment shutoff valve, union, and
plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook
up. NPT tap must be upstream from heater (see Figure 16).