Desa GA3700 Indoor Fireplace User Manual


 
www.desatech.com
113109-01G6
WARNING: This heater shall
      
-
    
-
National Fuel Gas
Code, ANSI Z223.1/NFPA 54, the
International Fuel Gas Code, or


     
  

Today’s homes are built more energy efcient
than ever. New materials, increased insulation
and new construction methods help reduce
heat loss in homes. Home owners weather
strip and caulk around windows and doors
to keep the cold air out and the warm air in.
During heating months, home owners want
their homes as airtight as possible.
While it is good to make your home energy efcient,
your home needs to breathe. Fresh air must enter
your home. All fuel-burning appliances need fresh
air for proper combustion and ventilation.
Exhaust fans, replaces, clothes dryers and
fuel burning appliances draw air from the house
to operate. You must provide adequate fresh
air for these appliances. This will insure proper
venting of vented fuel-burning appliances.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 6 through 8 will help
you classify your space and provide adequate
ventilation.

The air that leaks around doors and windows
may provide enough fresh air for combustion
and ventilation. However, in buildings of un-
usually tight construction, you must provide
additional fresh air.
AIR FOR COMBUSTION AND VENTILATION

construction where:
 -





2


and
 
and
  






If your home meets all of these three criteria,

Ventilation Air From Outdoors
If your home does not meet all of the three
Determining
Fresh-Air Flow For Heater Location

The National Fuel Gas Code, ANSI Z223.1/
NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per
1,000 Btu per hour (4.8 m
3
per kw) of the ag-
gregate input rating of all appliances installed
in that space and an unconned space as a
space whose volume is not less than 50 cubic
feet per 1,000 Btu per hour (4.8 m
3
per kw)
of the aggregate input rating of all appliances
installed in that space. Rooms communicating
directly with the space in which the appliances
are installed*, through openings not furnished
with doors, are considered a part of the un-
conned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation
grills between them.
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION


Use this work sheet to determine if you have
a conned or unconned space.
 Includes the room in which you will
install replace plus any adjoining rooms with
doorless passageways or ventilation grills
between the rooms.