While it is good to make your home energy ef-
cient, your home needs to breathe. Fresh air must
enter your home. All fuel-burning appliances need
fresh air for proper combustion and ventilation.
Exhaust fans, replaces, clothes dryers and fuel
burning appliances draw air from the house to
operate. You must provide adequate fresh air for
these appliances. This will insure proper venting
of vented fuel-burning appliances.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3,
Air for Combustion and Ventilation.
All spaces in homes fall into one of the three fol-
lowing ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 5 through 7 will help you
classify your space and provide adequate ventilation.
The air that leaks around doors and windows may
provide enough fresh air for combustion and ven-
tilation. However, in buildings of unusually tight
construction, you must provide additional fresh air.
construction where:
-
2
and
and
If your home meets all of these three criteria,
Ventilation Air From Outdoors
If your home does not meet all of the three
Determining
Fresh-Air Flow For Heater Location
The National Fuel Gas Code, ANSI Z223.1/NFPA
54 denes a conned space as a space whose
volume is less than 50 cubic feet per 1,000 Btu
per hour (4.8 m
3
per kw) of the aggregate input
rating of all appliances installed in that space and
an unconned space as a space whose volume is
not less than 50 cubic feet per 1,000 Btu per hour
(4.8 m
3
per kw) of the aggregate input rating of
all appliances installed in that space. Rooms com-
municating directly with the space in which the
appliances are installed*, through openings not
furnished with doors, are considered a part of the
unconned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation grills
between them.
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION
Use this work sheet to determine if you have a
conned or unconned space.
Includes the room in which you will install
replace plus any adjoining rooms with doorless pas-
sageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x
width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft.
(volume of space)
If additional ventilation to adjoining room is
supplied with grills or openings, add the volume
of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) x 20 =
51,200 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in
the space.
Vent-free replace ___________ Btu/Hr
Gas water heater* ___________ Btu/Hr
Gas furnace ___________ Btu/Hr
Vented gas heater ___________ Btu/Hr
Gas replace logs ___________ Btu/Hr
Other gas appliances* + ___________ Btu/Hr
Total = ___________ Btu/Hr
* Do not include direct-vent gas appliances. Di-
rect-vent draws combustion air from the outdoors
and vents to the outdoors.
AIR FOR COMBUSTION
AND VENTILATION
Continued