Desa CLD3018NA 24" Water Heater User Manual


 
107068
For more information, visit www.desatech.com
For more information, visit www.desatech.com
7
7
INSTALLATION
Check Gas Type
Installation and Clearances
WARNING: Never install the heater
in a bedroom or bathroom unless installed as a
vented appliance (Variable Manually-Controlled
Models Only) (see page 10)
in a recreational vehicle
where curtains, furniture, clothing, or other flam-
mable objects are less than 42 inches from the
front, top, or sides of the heater
in high traffic areas
in windy or drafty areas
WARNING: Seal any fresh air vents or ash clean-
out doors located on floor or wall of fireplace. If not,
drafting may cause pilot outage or sooting. Use a
heat-resistant sealant. Do not seal chimney flue
damper.
CAUTION: This heater creates warm air currents.
These currents move heat to wall surfaces next to
heater. Installing heater next to vinyl or cloth wall
coverings or operating heater where impurities (such
as, but not limited to, tobacco smoke, aromatic
candles, cleaning fluids, oil or kerosene lamps, etc.)
in the air exist, may discolor walls or cause odors.
IMPORTANT:
Vent-free heaters add moisture to the air. Although
this is beneficial, installing heater in rooms without enough venti-
lation air may cause mildew to form from too much moisture. See
Air for Combustion and Ventilation, pages 4 through 6.
CHECK GAS TYPE
Use only the correct gas type (natural or propane/LP) for your unit.
If your gas supply is not correct, do not install heater. Call dealer where
you bought heater for proper type heater.
INSTALLATION AND CLEARANCES
(Vent-Free Operation Only)
WARNING: Maintain the minimum clearances. If
you can, provide greater clearances from floor, ceil-
ing, and adjoining wall.
LOG SIZING REQUIREMENTS
Minimum Firebox Size
Log Front Rear
Size Height Depth Width Width*
18" 17" 14" 24" 20"
24" 17" 14" 28" 21"
MINIMUM FIREPLACE
CLEARANCE TO
COMBUSTIBLE MATERIALS
Log Size Side Wall Ceiling
18", 24" 16" 42"
*Measured at 14" Depth
INSTALLATION
Continued
Carefully follow the instructions below. This will ensure safe
installation into a masonry, UL127-listed manufactured fireplace,
or certified vent-free firebox.
Minimum Clearances For Side Combustible
Material, Side Wall, and Ceiling
A. Clearances from the side of the fireplace opening to any com-
bustible material and wall should follow diagram in Figure 4.
B. Clearances from the top of the fireplace opening to the ceiling
should not be less than 42 inches.
Figure 4 - Minimum Clearance for Combustible to Wall
*Minimum 16 inches from Side Wall
*