AIR FOR COMbUSTION
AND VENTILATION
Continued
The following are excerpts from National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3,
Air for Combustion and Ventilation.
All spaces in homes fall into one of the three fol-
lowing ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 5 through 7 will help
you classify your space and provide adequate
ventilation.
The air that leaks around doors and windows
may provide enough fresh air for combustion and
ventilation. However, in buildings of unusually
tight construction, you must provide additional
fresh air.
construction where:
-
-11
2
) or
and
and
If your home meets all of the three criteria
Ventilation Air From Outdoors,
If your home does not meet all of the three
Determining
Fresh-Air Flow For Heater Location
The National Fuel Gas Code, ANSI Z223.1/NFPA
54 denes a conned space as a space whose vol-
ume is less than 50 cubic feet per 1,000 Btu per hour
(4.8 m
3
per kw) of the aggregate input rating of all
appliances installed in that space and an unconned
space as a space whose volume is not less than 50
cubic feet per 1,000 Btu per hour (4.8 m
3
per kw) of
the aggregate input rating of all appliances installed
in that space. Rooms communicating directly with
the space in which the appliances are installed*,
through openings not furnished with doors, are
considered a part of the unconned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation grills
between them.
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION
Use this work sheet to determine if you have a
conned or unconned space.
Includes the room in which you will install
heater plus any adjoining rooms with doorless pas-
sageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x
width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft.
(volume of space)
If additional ventilation to adjoining room is
supplied with grills or openings, add the volume
of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) x 20 =
51,200 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in
the space.
Vent-free replace ___________ Btu/Hr
Gas water heater* ___________ Btu/Hr
Gas furnace ___________ Btu/Hr
Vented gas heater ___________ Btu/Hr
Gas replace logs ___________ Btu/Hr
Other gas appliances* + ___________ Btu/Hr
Total = ___________ Btu/Hr
* Do not include direct-vent gas appliances. Di-
rect-vent draws combustion air from the outdoors
and vents to the outdoors.