GAS RESIDENTIAL HEATERS
36"
3"
FLOOR
CEILING
Minimum
Minimum To Top Surface
Of Carpeting, Tile Or Other
Combustible Material
8"
Minimum
From
Sides Of
Heater
Right
Side
Left
Side
Figure 4 - Mounting Clearances As Viewed From Front of Heater
INSTALLING TO
WALL
NOTICE: A qualified service per-
son must install heater. Follow
all local codes.
CHECK GAS TYPE
Use only propane/LP. If your gas supply is
not propane/LP, do not install heater. Call
dealer where you bought heater for proper
type heater.
INSTALLATION ITEMS
Before installing heater, make sure you have
the items listed below.
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• manual shutoff valve *
• ground joint union
• test gauge connection * (see Figure
13, page 8)
• sediment trap
• tee joint
• pipe wrench
* An A.G.A. design-certified manual shutoff
valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Pur-
chase the optional A.G.A. design-certified
manual shutoff valve from your dealer. See
Accessory, page 12.
LOCATING HEATER
This heater is designed to be mounted on a
wall.
WARNING: Maintain the mini-
mum clearances shown in Figure
4. If you can, provide greater clear-
ances from floor, ceiling, and join-
ing wall.
WARNING: Never install the
heater
• in a bathroom
• in a recreational vehicle
• where curtains, furniture,
clothing, or other flammable
objects are less than 36 inches
from the front, top, or sides of
the heater
• as a fireplace insert
• in high traffic areas
• in windy or drafty areas
CAUTION: This heater cre-
ates warm air currents. These
currents move heat to wall sur-
faces next to heater. Installing
heater next to vinyl or cloth wall
coverings or operating heater
where impurities in the air (such
as tobacco smoke) exist, may
discolor walls.
IMPORTANT:
Vent-free heaters add mois-
ture to the air. Although this is beneficial,
installing heater in rooms without enough
ventilation air may cause mildew to form
from too much moisture. See Air for Com-
bustion and Ventilation, pages 3 through 5.
CAUTION: If you install the
heater in a home garage
• heater pilot and burner must
be at least 18 inches above
floor
• locate heater where moving
vehicle will not hit it
For convenience and efficiency, install heater
• where there is easy access for
operation, inspection, and service
• in coldest part of room