8
104416
UNVENTED NATURAL GAS LOG HEATER
DESA INTERNATIONAL
Heat Resistant
Material
(A)
Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.) Above Fireplace
Noncombustible
Material Distance (A) Requirements for Safe Installation
12" or more Noncombustible material OK.
Between 8" and 12" Install fireplace hood accessory (GA6050, GA6052,
or GA6053, see
Accessories
, page 25).
Less than 8" Noncombustible material must be extended to at
least 8". See
Between 8" and 12"
, above.
INSTALLATION
Continued
If Using Mantel
You must have noncombustible material(s)
above the fireplace opening. Noncombus-
tible materials (such as slate, marble, tile,
etc.) must be at least 1/2 inch thick. With
sheet metal, you must have noncombustible
material behind it. Noncombustible mate-
rial must extend at least 8 inches up. If
noncombustible material is less than 12",
you must install the fireplace hood acces-
sory (24" and 30" models only). Even if
noncombustible material is more than 12",
you may need the hood accessory to deflect
heat away from your mantel shelf. See Fig-
ure 5, and Figures 6 and 7, page 9, for
minimum clearances.
Minimum Noncombustible
Material Clearances
If Not Using Mantel
Note:
If using a mantel, proceed to If Using
Mantel. If not using a mantel, follow the
information below.
You must have noncombustible material(s)
above the fireplace opening. Noncombustible
materials (such as slate, marble, tile, etc.) must
be at least 1/2 inch thick. With sheet metal, you
must have noncombustible material behind it.
If noncombustible material is less than 12",
you must install the fireplace hood accessory
(24" and 30" models only). See Figure 5 for
minimum clearances.
IMPORTANT:
If you cannot meet these
minimum clearances, you must operate
heater with chimney flue damper open. Go
to Installing Damper Clamp Accessory for
Vented Operation, page 10.
NOTICE: Manual control heaters
may be used as a vented product.
If so, you must always run heater
with chimney flue damper open.
If running heater with damper
open, noncombustible material
above fireplace opening is not
needed. Go to
Installing Damper
Clamp Accessory for Vented
Operation
, page 10.
IMPORTANT:
If you cannot meet these
minimum clearances, you must operate
heater with chimney flue damper open. Go
to Installing Damper Clamp Accessory for
Vented Operation, page 10.