MULTIFUNCTION LCD READOUT
BASIC OPERATION
Screen toggle – To toggle through the status screens press the Select button which is located directly next to the
LCD.
Screen illumination– After 30 seconds of inactivity, the LCD backlight will automatically turn off to conserve
energy. Keeping the LCD screen lit at all times is not an option on this UPS.
Select Button
If the LCD screen is not lit pressing the Select button once will turn the LCD on. If the LCD screen is lit, then
pressing the Select button once will toggle through the status screens.
Pressing and holding the Select button for four (4) seconds while UPS is in Normal operation will initiate the Self
Test.
Pressing and holding the Select button for four (4) seconds while UPS is in Battery/Offline mode will activate Silent
Mode on the UPS.
MAIN FEATURES
The multifunction LCD readout provides ready access to power/battery condition vitals, such as:
Runtime, Load, Temperature, and much more.
The screen is also rotatable so the UPS can be used in either rack mount or vertical/tower
orientation.
Select Button
DEFINITION FRO ILLUMINATED LCD INDICATORS
Load Level:
The total
load of the connected
equipment shown in
20% increments.
Battery Capacity:
The
battery’s current charge
level shown in 20%
increments.
Fault icon:
This icon appears if there is
an internal problem with the UPS.
Please contact Technical Support if
this icon is lit.
Normal Icon:
This icon
appears when the UPS
is working under normal
conditions.
Battery Icon:
This icon appear
s when the UPS is
operating using battery power. The UPS will also
sound alarms (two short beeps followed by a pause)
when this icon is lit. When the Battery Icon is lit and
the Battery Capacity falls to 20% the frequency of
the alarms will increase indicating that the UPS
batteries are nearly out of power. If this occurs, it is
recommended that you either restore AC power, or
manually power down your equipment that may be
negatively affected by sudden power loss.
Automat
ic Voltage Regulation (AVR) icon:
This icon
appears when the UPS is automatically correcting
AC input line voltage without using battery power.
This is a normal, automatic operation of your UPS,
and no action is required. The AVR in this UPS
continuously conditions the power to a nominal 208V
output to connected equipment. In the event of a
complete power loss, severe brownout, or over
voltage, the UPS relies on its internal battery back
up to supply a consistent 208V output.
Silent icon:
This icon appears when the
UPS is in silent mode. During Silent mode,
the unit’s alarm does not sound until the
Battery Capacity falls to < 20%.
Overload icon:
This icon appears
when the Battery/Surge outlets on the
UPS are overloaded. The UPS will
also sound an alarm at this point. To
clear the overload, the total load of the
connected equipment must be less
than the unit’s maximum capability.
The easiest way to correct this
problem is to remove noncritical
equipment from the Battery/Surge
outlets.