Tee Pipe Cap
Joint Nipple
INSTALLATION
Continued
WARNING: Never use an open flame to check for
a leak. Apply a noncorrosive leak detection fluid to all
joints. Bubbles forming show a leak. Correct all leaks
at once.
WARNING: Test all gas piping and connections,
internal and external to unit, for leaks after installing
or servicing. Correct all leaks at once.
CHECKING GAS CONNECTIONS
Pressure Testing Gas Supply Piping System
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1. Disconnect appliance with its appliance main gas valve (control
valve) and equipment shutoff valve from gas supply piping sys-
tem. Pressures in excess of 1/2 psig will damage heater regulator.
2. Cap off open end of gas pipe where equipment shutoff valve
was connected.
3. Pressurize supply piping system by either using compressed
air or opening propane/LP supply tank valve.
4. Check all joints of gas supply piping system. Apply noncorrosive
leak detection fluid to gas joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff valve to gas supply.
Check reconnected fittings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 20).
2. Pressurize supply piping system by either using compressed air or
opening propane/LP supply tank valve.
3. Check all joints from gas meter to equipment shutoff valve (see
Figure 21). Apply noncorrosive leak detection fluid to gas joints.
Bubbles forming show a leak.
4. Correct all leaks at once.
CAUTION: Make sure external regulator has been
installed between propane/LP supply and heater. See
guidelines under
Connecting to Gas Supply
, page 11.
CAUTION: Avoid damage to regulator. Hold gas
regulator with wrench when connecting it to gas
piping and/or fittings.
We recommend that you install a sediment trap in supply line as
shown in Figure 19. Locate sediment trap where it is within reach for
cleaning. Install in piping system between fuel supply and heater.
Locate sediment trap where trapped matter is not likely to freeze. A
sediment trap traps moisture and contaminants. This keeps them
from going into heater controls. If sediment trap is not installed or
is installed wrong, heater may not run properly.
Figure 19 - Gas Connection
* Purchase the optional CSA design-certified equipment shutoff
valve from your dealer. See Accessories, page 19.
**Minimum inlet pressure for purpose of input adjustment.
3" Minimum
Sediment Trap
Gas
Regulator
From External
Regulator (11"
W.C.** to 14"
W.C. Pressure)
CSA Design-Certified
Equipment Shutoff Valve
With 1/8" NPT Tap*
Approved Flexible
Gas Hose (if allowed
by local codes)
O
N
POSI
T
O
PO
S
Figure 20- Equipment Shutoff Valve
Closed
Equipment
Shutoff
Valve
Open
Figure 21 - Checking Gas Joints
Control Valve Location
Propane/LP
Supply Tank
Equipment
Shutoff Valve
INSTALLATION
Connecting to Gas Supply (Cont.)
Checking Gas Connections