AIR FLOW DATA
HIGH / LOW SPEED COOLING AND HEAT PUMP CFM - WITHOUT FILTERS
FC9V060B12DH11 FC9V080B12DH11 Jumper Settings
High Low High Low COOL Tap ADJ Tap
1329 898 1312 878 A B
1133 774 1117 741 B B
1226 842 1202 810 A A
1039 708 996 683 B A
1110 755 1084 725 A C
915 637 892 618 C B
930 646 898 619 B C
719 529 700 511 D B
856 603 827 580 C A
657 526 642 500 D A
762 566 746 532 C C
612 523 596 500 D C
FC9V080C16DH11 FC9V100C20DH11 Jumper Settings
High Low High Low COOL Tap ADJ Tap*
1758 1183 2196 1498 A B
1646 1106 1858 1167 B B
1699 1140 2045 1363 A A
1531 1033 1661 1054 B A
1527 1047 1884 1201 A C
1449 969 1597 1022 C B
1368 930 1506 947 B C
1213 832 1395 891 D B
1309 897 1477 922 C A
1116 762 1254 761 D A
1170 808 1304 801 C C
1031 703 1114 657 D C
FC9V120D20DH11
Jumper Settings
High Low
COOL Tap ADJ Tap*
2342 1528
AB
1904 1229
BB
2140 1404
AA
1700 1096
BA
1918 1247
AC
1643 1044
CB
1522 967
BC
1418 852
DB
1494 945
CA
1287 772
DA
1337 802
CC
1132 668
DC
HIGH / LOW HEAT CFM - WITHOUT FILTERS
FC9V060B12DH11 FC9V080B12DH11 Jumper Settings
High Low High Low HEAT Tap ADJ Tap*
1137 720 1386 962 A Any
974 625 1322 892 B Any
883 593 1250 849 C Any
825 561 1159 768 D Any
FC9V080C16DH11 FC9V100C20DH11 Jumper Settings
High Low High Low HEAT Tap ADJ Tap*
1732 1173 1912 1237 A Any
1631 1110 1688 1079 B Any
1493 1008 1545 967 C Any
1359 931 1422 899 D Any
FC9V120D20DH11
Jumper Settings
High Low
HEAT Tap ADJ Tap*
2238 1465
AAny
2014 1313
BAny
1863 1211
CAny
1686 1075
DAny
All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to
0.6” w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0”
w.c. external static pressure is not recommended.
NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower that what is required to operate an airflow switch on certain models of electronic
air cleaners. Consult the instructions for the electronic air cleaner for further details.
* The ADJ “D” tap should not be used.