Vermont Casting MO18 Indoor Fireplace User Manual


 
20012914 7/05 Rev. 0
4
1
Listing and Code Approvals
A. Appliance Certication
The Gas Log Hearth Kits have been tested and listed in the
U.S. in accordance with ANSI Z21.84-2003 (Gas Log Set).
They have been listed by OMNI Test Labs for installation and
operation in the United States and Canada as described in
these Installation and Operating Instructions. All components
are UL, OMNI or CSA safety certied.
Check with your local building code agency prior to installing
this appliance to ensure compliance with local codes,
including the need for permits and follow-up inspections. In
the absence of local codes, comply with the National Fuel
Gas Code, ANSI Z223.1-Latest Edition in the U.S. If any
assistance is required during installation, please contact
your local dealer.
B. Table 1
Improper installation, adjustment, alteration, service
or maintenance can cause injury or property damage.
Refer to the owner’s information manual provided with
this appliance. For assistance or additional information
consult a qualied installer, service agency or the gas
supplier.
WARNING
Fire Risk
Exhaust Fumes Risk
Do NOT use this appliance as a “vent-free
heater.
The ue must be permanently open. Refer
to Table 1.
WARNING
Product 18” 24”
Inlet BTU Nat. 67,000 68,000
Max. Inlet Pressure
IN. WC / KPa
Nat. 10.0 / .052 10 / .052
Min. Inlet Pressure IN.
WC / KPa
Nat. 3.5 / .018 3.5 / .018
Orice Size
In.
Nat. (#28) (#26)
Minimum Fireplace
Opening Size
In. / cm
Front 33 38
Rear 20 26
Depth 15 15
Height 21 21
Min. Vent Opening in
Square In. / cm
39 / 251.6 48 / 309.7
These Hearth/Log Kits are for use with all CFM Factory built replaces.