Vermont Casting DBR39 Indoor Fireplace User Manual


 
- 6 -
Do not use this fireplace if any part of it has
been under water. Immediately call a qualified
service technician to inspect the fireplace
and replace any part of the control which has
been under water.
Cold climate installation recommendation:
When installing this unit against a non-
insulated exterior wall or chase, it is
mandatory that the outer walls be insulated
to conform to applicable insulation codes.
Non-combustible materials such as brick and tile can be
extended over the outer face of the unit (Do not cover
louvres or glass door). If a Trim Kit is going to be installed,
brick and tile will have to be installed flush with the side of
this appliance.
FINAL FINISHING
HEARTH
A hearth is not mandatory but it is recommended for
aesthetic purposes. We recommend a non-combustible
hearth which does not obstruct louvre opening.
GAS SPECIFICATIONS
MAX. MIN.
INPUT INPUT
MODEL FUEL GAS CONTROL B.T.U.H B.T.U.H.
DBR33 RN Natural Gas Millivolt Hi/Lo 15,000 10,500
DBR33 RP Propane Gas Millivolt Hi/Lo 15,000 11,250
DBR36 RN Natural Gas Millivolt Hi/Lo 18,000 12,600
DBR36 RP Propane Gas Millivolt Hi/Lo 18,000 13,500
DBR39 RN Natural Gas Millivolt Hi/Lo 22,000 15,400
DBR39 RP Propane Gas Millivolt Hi/Lo 22,000 16,500
CERTIFIED TO:
ANSI Z1.88b-1999/CSA Z2.33-M-99 harmonized,
standard for Vented Gas Fireplace.
Table 6
The installation of your Fireplace must
conform with local codes, or in the absence
of local codes, with National Fuel Gas Code,
ANSI Z223.1 — latest edition, or CAN 1 B1-
149.1 and .2 Installation Code. (EXCEPTION:
Do not derate this appliance for altitude.
Maintain the manifold pressure at 3.5 inches
W.C. for Natural Gas and 10 inches W.C. for
LP gas.)
GAS INLET & MANIFOLD PRESSURES
Input Minimum
Input Maximum
Manifold Pressure
NATURAL
LP (Propane)
11" wc
13" wc
10" wc
4.5" wc
7" wc
3.5" wc
Table 7